DIAGNOSTICS

7.1 - Messages on turning on

When the control unit is switched on, the behaviour of the OK led is significant as shown in Table 5, in particular:
- if learning the opening and closing positions is correct
- if learning the safety device ( sensitive edge) is correct and what type of device has been recognized..

TABLE 5

Signal when the control unit is switched on

Behaviour of the OK led

Clear memory (no position or safety acquired)

Quick flashing for 5 seconds - green

Positions acquired and STOP 8.2KΩ

1 slow flash - red

Positions acquired and STOP OSE

2 slow flashes - red

Motor with electromechanical limit switch

1 slow flash - green

Motor with incremental encoder

2 slow flashes - green

Motor with absolute encoder

3 slow flashes - green

After the messages shown in Table 5, the control unit shows any errors: see paragraph 7.2.

6.3 - Connecting a buffer battery

The control unit is prepared for the installation of the buffer bat-

tery mod. PS224 (optional accessory): 7.2 Ah with built-in battery 

charger. 

To connect the buffer battery, proceed as shown on the side.

 CAUTION! - The electrical connection of the buffer battery 

to the control unit must be done only after completing all the 

installation and programming phases, since the battery is an 

emergency supply.

6.4 - Connecting the status light and diagnostics

The control unit is ready for the connection of a 24 V - 5 W max 

warning light to the “light” terminal of the button panel board inside 

the box lid (picture on the side: terminal 1 - 2+).
The “light” can be installed on the same box lid making a hole or out 

of the control unit at a maximum distance of 2 m from it.

 WARNING - The output is not protected against shortcir-

cuits.

This “light” works as follows:

OFF

 = when the safety chain is open (ing ALT, STOP button, red 

or release)

flashing

 (0.5 s ON, 0.5 s OFF) = when it works correctly

- behaviour as the diagnostics of the OK led, red = when some 

components require diagnostics.

1 2

- +

6.5 - Open and Close block (using the buttons on the 

box lid)

In the button panel board inside the box lid, there is a two-way dip 

switch that allows activating the Open and Close buttons.

OFF position

 = the buttons are disabled.

ON posi

tion

 = the buttons are enabled.

 WARNING - The STOP button is always active.
 WARNING - To perform the learning procedures, the dip 

switches must be activated to be able to use the buttons.

ON

OFF

Summary of Contents for DPRO924

Page 1: ...DPRO924 Nice Control unit EN Instructions and warnings for installation and use...

Page 2: ...C A D F E B 9 6 5 8 2 3 8 4 4 7 1 2 1 210 125 310 125 310 I...

Page 3: ...3 A B 4 A B C 6 1 2 1 2 FUSE FUSE OXI New Generetion OXI SMXI II...

Page 4: ...tal deletion of the control unit s memory 6 4 3 Learning about the safety devices and DIP SWITCH programming 6 4 4 Learning about the Opening and Closing positions with an incremental encoder 6 4 5 Op...

Page 5: ...product as described in this instruction manual and for certain types of use e g excluding use solely for vehicles may cause the product to fall within the scope of Regulation No 305 2011 and its har...

Page 6: ...he ducting for routing the electrical cables and for the cable entry point into the control unit housing be aware that due to possible deposits of water in the junction wells the connection ducts migh...

Page 7: ...unit 1 24V motor 2 24V motor 3 motor Limit Switch function unavailable Connector for the electromechanical limit switch connection Common limit switch common Open input of maximum opening limit switch...

Page 8: ...stance output During the recognition phase the control unit recognises the type of device con nected and causes a STOP whenever any variation in the recognised status occurs Multiple devices even of d...

Page 9: ...ed system in a thorough and rapid manner You can connect Oview to the control unit via the IBT4N interface using a bus cable with 4 wires inside To access the BusT4 connector you need to open the cont...

Page 10: ...door Opening and Closing positions must be carried out one after the other and without interruptions They cannot be performed at different times CAUTION Procedure for motors with incremental encoders...

Page 11: ...y to set the dip switches to OFF TABLE 3 DIP SWITCH A DIP1 DIP2 DIP3 DIP4 Function OFF OFF OFF OFF Hold to run movement ON X OFF OFF Acquisition of positions and status of the ALT input OFF ON OFF OFF...

Page 12: ...10 years This must include at least an assembly drawing of the automated system a wiring diagram an analysis of hazards and solutions adopted a manufacturer s declaration of conformity of all the devi...

Page 13: ...Connecting photocells in Phototest mode The Phototest function increases the reliability of the safety devices allowing reaching category II in compliance with the EN 13849 1 standard set of the contr...

Page 14: ...e CAUTION The electrical connection of the buffer battery to the control unit must be done only after completing all the installation and programming phases since the battery is an emergency supply 6...

Page 15: ...shing light the diagnostics signals continue for two sequences of flashes e g 3 flashes short pause 3 flashes long pause repeated twice Configured with the Oview programmer as Flashing Light 1 TABLE 7...

Page 16: ...iew OUT3 output With clean contact relay programmable with Oview Aerial input 52ohm for RG58 type cable or similar for OXI New Generetion use the aerial connector on the receiver STOP input For contac...

Page 17: ...n the product conforms to the following directive in accordance with the provisions applicable to partly completed machinery Directive 2006 42 EC OF THE EUROPEAN PARLIAMENT AND COUNCIL of May 17 2006...

Page 18: ...www niceforyou com Nice SpA Via Callalta 1 31046 Oderzo TV Italy info niceforyou com IS0662A00MM_31 07 2018...

Reviews: