MENU 5.1.5 - FAN SP. EXHAUST AIR
(ACCESSORY IS REQUIRED)
normal and speed 1-4
Setting range: 0 – 100 %
Factory setting normal: 65 %
Factory setting speed 1: 0 %
Factory setting speed 2: 30 %
Factory setting speed 3: 80 %
Factory setting speed 4: 100 %
Set the speed for the four different selectable modes for
the fan here.
Caution
An incorrectly set ventilation flow can damage the
house and may also increase energy consumption.
MENU 5.1.10 - OP. MOD HEAT MED PUMP
op. mode
Setting range: auto,
Default value: auto
Set the operating mode of the heating medium pump here.
auto: The heating medium pump runs according to the cur-
rent operating mode for VVM 310.
MENU 5.1.11 - PUMP SPEED HEATING MEDIUM
speed in wait mode
Setting range: 1 - 100 %
Default values: 30 %
min. allowed speed
Setting range: 1 - 50%
Default values: 1 %
max. allowed speed
Setting range: 50 - 100 %
Default values: 100 %
speed active cooling (accessory is required)
Setting range: 1 - 100 %
Default values: 70 %
speed passive cooling (accessory is
required)
Setting range: 1 - 100 %
Default values: 70 %
op. mode
Setting range: auto / manual
Default value: auto
auto: The heating medium pump’s speed is regulated for
optimum operation.
manual: The speed of the heating medium pump can be set
between 0 and 100 %.
If there are accessories for cooling present or if the heat
pump has a built-in function for cooling you can also set
the heating medium pump speed during active respectively
cooling operating modes (the heating medium pump then
runs in manual operation).
MENU 5.1.12 - INTERNAL ELECTRICAL
ADDITION
max connected el. add.
Setting range: 0–12 kW
Default values: 8 kW
fuse size
Setting range: 1 - 400 A
Factory setting: 16 A
Here you set the max. electrical output of the internal elec-
trical addition in VVM 310 and the fuse size for the installa-
tion.
Here you can also check which current sensor is installed
on which incoming phase to the property (this requires
current sensors to be installed, see page 24). Check by se-
lecting “detect phase order” and pressing the OK button.
The results of these checks appear just below the menu
selection "detect phase order".
MENU 5.1.13 - MAX INST. EL.PWR (BBR)
max installed el.pwr (only this machine)
Setting range: 0.000 - 30.000 kW
Default values: 15.000 kW
If the above building regulations are not applicable, do not
use this setting.
In order to meet certain building regulations, it is possible
to lock the device's maximum power output. In this menu,
you can set the value corresponding to the heat pump's
maximum power connection for heating, hot water and
cooling, if applicable Note whether there are also external
electrical components that are to be included. After the
value has been locked, a weeks cooling-off period starts.
After this period, parts in the machine must be replaced in
order to obtain greater power.
NIBE VVM 310
Chapter 8 | Control – Menus
44