Sweeping
!
WARNING!
The current to the boiler must be switched off during
service and maintenance of the boiler and burner!
The boiler must be swept and emptied of ash regularly.
Sweeping description
First ensure that the current to the boiler is OFF and that
the boiler has cooled down!
Before the sweep visits, the hatch for the draft limiter must
be locked by turning the locking screw a quarter turn to
the side of the hatch. This is to prevent soot from entering
the boiler room when the chimney is swept. After sweep-
ing, the hatch must be relocked.
PELLUX 100 swept by pulling through the channels in the
boiler's convection section with the supplied soot brush
and vacuuming the hearth.
The turbulators must be removed before the ducts are
swept, see
Remove the turbulators
page 58.
After completed cleaning, the turbulators are installed
and the soot hatch is reinstalled.
The soot that is released during sweeping is partially col-
lected in the ash box, partially in the soot box which must
be emptied. Open the boiler door, first unscrew the ash
and then the soot box and empty them. Reinstall them in
the relevant location. Take care to slide in the ash box as
far as possible.
APH
NOTE
Ash can still contain glowing embers after a long
period of time. Therefore, always use a non-inflam-
mable container and protective gloves when empty-
ing ash and soot.
Remove the turbulators
!
WARNING!
The current to the boiler must be switched off during
service and maintenance of the boiler and burner!
APH
1. Open the soot hatches by slackening off the outer
knobs.
2. Pull the lever under the turbulator pairs until it is in its
uppermost position. The turbulators can be removed
in their pairs.
APH
PELLUX 100
58