By unpacking the equipment from the wooden case remove all screws.
1.3.4 NAMEPLATE
The technical specifications of the Equipment are provided on the nameplate, which is situated at the front (internal
door) of the UPS. Check if it corresponds to the purchased material mentioned in the delivery note. For cabinets
A&B the nameplate will be positioned on the rear side, for cabinet C at the front behind the cover.
1.3.5 BATTERIES AND STORAGE
The standard batteries of the UPS are sealed, maintenance-free batteries, mounted usually in an external battery
cabinet and will typically be connected when the UPS is commissioned.
The battery life depends very much on the ambient temperature. A temperature range b18° and +23°C
will achieve the optimum battery life.
If the UPS is delivered without batteries, NEWAVE is not responsible for any damage or malfunctioning caused to
the UPS by incorrect wiring.
1.3.5.1
Storage of battery
The battery life depends very much on the ambient temperature. It is therefore important not to store the battery
longer than 6 months at 20°C, 3 months at 30°C and 2 months at 35°C storage temperature without a battery
recharge. For long-term storage make sure that the battery is fully recharged every 6 months. Before and after
storing, charge the battery.
Always store the batteries in a dry, clean, cool environment in their original packaging. If the packing container is
removed protect the batteries from dust and humidity.
Bottom screws
Sides screws