Section-10
www.newavenergy.com
04-1206_S10_NW_TDSPS_10-50kVA_GB_110201.DOC
Page 9/19
Printed in Switzerland – Modifications reserved
10.6 ENVIRONMENTAL
CHARACTERISTICS
UPS range
10kVA
15kVA
20kVA
25kVA
30kVA
40kVA
50kVA
Audible Noise with
100% / 50% Load
dBA
55/49
55/49
57/49
57/49
58/50
59/50
59/50
Operation temperature
°C
0 – 40
Ambient Temperature
for Batteries
(recommended)
°C
20 – 25
Storage Temperature
°C
-25 - +70
Battery Storage Time at
Ambient Temperature
Max. 6 months
Max. altitude (above sea
level)
m
1000m (3300ft) without de-rating
Meter above sea level (m / ft)
De-Rating Factor for Power
1500 / 4850
0.95
2000 / 6600
0.91
2500 / 8250
0.86
De-rating factor for use
at altitudes above
1000m sea level
according
( IEC 62040-3)
3000 / 9900
0.82
Relative Air-humidity
Max. 95% (non-condensing)
Accessibility
Rear access
Front access
Positioning
Min. 20 cm rear space (required for fan)
Input and Output Power
Cabling
Rear side bottom
Front side bottom
Efficiency AC-AC
(
depending on power rating)
%
Load
:
100 %
75 %
50%
25%
95.5% 95.5%
95% 94.5%
Eco-Mode efficiency at
100% load
%
98 %
10.7 STANDARDS
Safety
IEC/EN 62040-1, IEC/EN 60950-1
Electromagnetic Compatibility
IEC/EN 62040-2, IEC/EN61000-3-2,
IEC/EN61000-6-2,
EMC Classification for
10kVA
15-50kVA
Emission Class
C2
C3
Immunity Class
C3
Performance
IEC/EN62040-3
Product certification
CE
Degree of protection
IP 20