The UPS may contain batteries that must be re-charged for a minimum of 24 hours every 6 months to
prevent deep discharging. Batteries that have been, for whatever reason, deep discharged are not covered
by the warranty.
1.2.8 EXTENDED WARRANTY
The local office or distributor may grant a Extended Warranty period different to the above twelve (12) months and
refer to local terms of liability as defined in the supply agreement or maintenance contract.
For more details please contact the nearest local office or agent authorized by the manufacturer.
(
www.newavenergy.com
Resellers).
1.3
DELIVERY – TRANSPORT - STORAGE
1.3.1 INTRODUCTION
This chapter contains all the necessary information for the correct unpacking, positioning, cabling and installation
of the UPS
The UPS and accessories are delivered on a specifically designed pallet that is easy to move with a forklift or a
pallet jack. Keep the UPS always in upright position and do not drop the equipment. Do not either stack the pallets
because of high-energy batteries involved and the heavy weight
NOTE!
IF THE UPS IS NOT IMMEDIATELY INSTALLED THE FOLLOWING GUIDELINES
MUST BE FOLLOWED:
TRANSPORT:
UPS CABINETS AND/OR BATTERY CABINET CAN FALL OVER. USE THE
SHIPPING BRACKETS ON THE REAR AND FRONT TO SECURE THE
CABINETS. DO NOT TILT THEM MORE THAN 10° FROM VERTICAL,
OTHERWISE CABINETS MAY TIP OVER.
POTENTIAL DANGERS:
•
TILTING THE CABINET MIGHT DAMAGE THE SYSTEM AND
THEREFORE SHOULD NO LONGER BE CONNECTED TO THE MAINS.
•
WEIGHT OF THE UPS SYSTEM COULD CAUSE SERIOUS INJURIES TO
PERSONS OR ANYTHING IN THE SURROUNDING AREA.
STORAGE:
•
THE UPS SHOULD BE STORED IN THE ORIGINAL PACKING AND
SHIPPING CARTON
•
THE RECOMMENDED STORING TEMPERATURE FOR THE UPS
SYSTEM AND BATTERIES IS B5 °C AND +40°C.¨
•
THE UPS SYSTEM AND THE BATTERIE SETS MUST BE PROTECTED
FROM HUMIDITY < 90% RF (NON-CONDENSING).
1.3.2 RECEIPT OF THE UPS AND VISUAL INSPECTION
Upon receiving the UPS, carefully examine the packing container and the UPS for any sign of physical damage.
The outside ’Tip&Tel’ ( "FRAGILE" and "ARROW") indicator should be intact if the equipment has been transported
in the upright position. In case of rupture or suspect inform immediately:
•
The carrier and
•
NEWAVE SA.
!