22
P r O g r a m m i N g
Prog
neSS D24 Control Panel - inStallation & PrograMMing Manual
maP ZONES TO OuTPuT grOuPS
these options set the output groups which any zone will trigger when alarmed.
Zones can be setup to trigger a different output in each panel state.
P35xxe ArmeD
Map zones to output groups to be triggered when the panel is armed.
P35
[output group 0–31]
e
[Zone number]
e
[Zone number]
e
...etc
Factory default setting is all zones mapped to output group 17. P3517e will show
all 24 zones on.
P36xxe DISArmeD
Map zones to output groups to be triggered when the panel is Disarmed.
P36
[output group 0–31]
e
[Zone number]
e
[Zone number]
e
...etc
Factory default setting is all zones mapped to output group 0. P360e will show all
24 zones on.
This means that all zones are disabled when the panel is disarmed.
P37xxe moNItor moDe
assign zones to output groups to be triggered when the panel is in Monitor mode.
P37
[output group 0–31]
e
[Zone number]
e
[Zone number]
e
...etc
Factory default setting is all zones mapped to output group 20. P3720e will show
all 24 zones on.
To remove a zone from Monitor mode, assign it to Output Group P370E.
P38xxe 24Hr ZoNeS
Create 24hr zones by mapping zones to output groups in this option.
P38
[output group 0–31]
e
[Zone number]
e
[Zone number]
e
...etc
Factory default setting is all zones mapped to output group 0. P380e will show all
24 zones on.
This means that no zones are 24hr zones.
P35xxe – P38xxe
prOgraM MOde leVel:
Installer, Remote by PC
FaCtOrY deFault:
[see table]
tO prOgraM:
p
[Option No]
e
[Output Group]
e
[Zone]
e
Maps zones to the selected output group.
nOtes:
• Zones can be disabled by mapping them to
Output group 0.
• Zones are removed from an output group by
mapping them to a different output group.
• Output Groups list, see page 24
OPTION No
PANEL STATE
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Zones
P35xxE
P36xxE
P37xxE
P38xxE
ARMED
DISARMED
MONITOR MODE
24hr ZONES
Choose an Output Group (0-31)
Turn ON the zones required to be in the selected Output Group
eXaMple 1:
To make zones 23 & 24 into 24hr zones by
mapping them to output group 17.
P3817e 23e 24e
eXaMple 2:
To map zones 1, 2 3 & 4 to output group 20
when Armed.
P3520e 1e 2e 3e 4e
FaCtOrY deFaults
armed: P35
17
e - all zones selected on, (output group 17).
Disarmed: P36
0
e - all zones selected on, (output group 0, disabled).
Monitor mode: P37
20
e - all zones selected on, (output group 20).
24hr zones: P38
0
e - all zones selected on, (output group 0, disabled).
Note: xx refers to the output group number.
See the output groups table on page 24.