5. COMMISSIONING   

WARNING: 

CONNECT BDM-300X2 TO THE ELECTRICAL UTILITY GRID ONLY AFTER RECEIVING 

PRIOR APPROVAL FROM THE UTILITY COMPANY. 

WARNING: 

BE AWARE THAT ONLY QUALIFIED PERSONNEL CAN CONNECT BDM-300X2 TO 

THE ELECTRICAL UTILITY GRID.   

WARNING:

 

ENSURE THAT ALL AC AND DC WIRING IS CORRECT. ENSURE THAT NONE OF THE 

AC AND DC WIRES IS PINCHED OR DAMAGED. ENSURE THAT ALL JUNCTION BOXES ARE 

PROPERLY CLOSED.     

Following these steps to commission the BDM-300X2 PV system:   
1. Turn on the AC disconnects or circuit breakers on each BDM-300X2 AC branch 

circuit.   

2. Turn on the main u

�li

ty-grid AC circuit breaker. Your system will start producing 

power a

er a few minutes wait 

me.   

3. The BDM-300X2 will start to send performance data over the power lines using 

power line communica

on (PLC) to the BDG-256. The 

me required for each BDM-

300X2 in the system to communicate to the BDG-256 will vary with the number of 

BDM-300X2 in the system.   

 

 

6. OPERATING INSTRUCTIONS

   

The BDM-300X2 is powered on when su

cient DC voltage from the module is 

applied. The status LED will start 

ashing a

er su

cient DC power is applied as an 

indica

on that the BDM-300X2 is live.   

Status: standby   

The LED light is on by 2 second, and o

 by 2 seconds

Red: in error.
O

range: no error, but not communicating to BDG-256

Green: no error, and communica

ng to BDG-256 

Status: pr

o

ducing p

o

wer   

The LED light is on by 1 second, and o

 by 1 second. 

Orange: not communica

ng to BDG-256

Green: communica

ng to BDG-256   

 

 

Status: gr

o

unding fault   

The LED light is in 

solid red

 color.   

In case of fault, BDM-250 has mul

ple protec

�v

e func

ons and stops output power.   

The fault message may be sent to a connected BDG-256 gateway through power 

line communica

on.  The error message is displayed on the screen of BDG-256 

gateway by a 16-bit error code.     
 

Err

o

r c

o

de 

Err

o

Bit-0 

DC over voltage 

Bit-1 

DC under voltage 

Bit-2 

hardware error 

Bit-3 

Inverter over voltage 

Bit-4 

Frequency over 

Bit-5 

Frequency under 

Bit-6 

AC voltage RMS over 

Bit-7 

AC voltage RMS under 

Bit-8 

Peak AC voltage over 

Bit-9 

AC current RMS over 

Bit-10 

Peak AC current over 

Bit-11 

Temperature over 

Bit-12 

ADC error 

Bit-13 

GFDI fault indicator 

Bit-14 

Relay fault (BDM-250-AU/BDM-250-EU only) 

Bit-15 

PLC Communica

on Error   

 

7. TROUBLESHOOTING AND MAINTENANCE 

WARNING: 

DO NOT ATTEMPT TO REPAIR THE BDM-300X2; IT CONTAINS NO USER-

SERVICEABLE PARTS. IF TROUBLESHOOTING METHODS FAIL, PLEASE RETURN THE BDM-300X2 

TO YOUR DISTRIBUTOR FOR MAINTENANCE.   

WARNING: 

NEVER DISCONNECT THE DC WIRE CONNECTORS UNDER LOAD. ENSURE THAT 

NO CURRENT IS FLOWING IN THE DC WIRES PRIOR TO DISCONNECTING. AN OPAQUE 

COVERING MAY BE USED TO COVER THE MODULE PRIOR TO DISCONNECTING   

WARNING: 

BDM-300X2 IS POWERED BY DC POWER FROM PV MODULES. MAKE SURE YOU 

DISCONNECT THE DC CONNECTIONS AND RECONNECT DC POWER TO WATCH FOR THE TWO 

SECONDS LED ON AND TWO SECONDS LED OFF AFTER DC IS APPLIED.   

 

11

10 

Summary of Contents for BDM-300X2-208A

Page 1: ... 3252 FAX 81 092 433 3171 China Address No 1 Anhe Rd Tsingtao Export Processing Zone Tsingtao China 266113 TEL 86 532 87963900 FAX 86 532 81100917 Email info northernep com Web h p www northernep com h p www nep japan com h p www micro inverter jp Rev 2017 01 12 BDM 300X2 240A D BDM 300X2 208A D BDM 300X2 AU D BDM 300X2 EU D Installa on and Opera on Manual ...

Page 2: ...on Procedure Step 1 Install the AC Branch Circuit Junc on Box Step 2 A ach the BDM 300X2 to the Racking Step 3 Connect the BDM 300X2 Wiring Harnesses Step 4 Ground the System Step 5 Complete the connec on map and connect the PV Modules 5 COMMISSIONING 6 OPERATING INSTRUCTIONS 7 TROUBLRSHOOTING MAINTENANCE 8 SPECIFICATION 9 WARRANTY AND PRODUCTION INFORMATION CONTENTS 01 02 02 02 02 02 03 03 04 04 ...

Page 3: ...mmunity and powered by electricity from solar wind and micro turbines Outside China the company has opera on offices in Chicago U S and Vancouver Canada The technology founders of the company are well known experts in the fields of power electronics automa c control signal processing and communica ons Each of the founders has mul ple U S and world patents in their specialty areas They received Ph D d...

Page 4: ...NVERTER SHOULD BE MODIFIED ALL INSTALLATION SHOULD FOLLOW THE LOCAL ELECTRIC CODES FURTHER PROTECTION ON THE AC WIRING FROM THE INVERTERS SHOULD BE PROVIDED AND MAY BE REQUIRED BY LOCAL AND NATIONAL WIRING REGULATIONS THIS PROTECTION IS LIKELY TO INCLUDE RESIDUAL CURRENT DEVICES EARTH FAULT MONITORS AND CIRCUIT BREAKERS THIS PRODUCT MAY CAUSE AC CURRENT WITH A DC COMPONENT IF A RESIDUAL CURRENT OP...

Page 5: ...st prac ce to install surge protec on as part of any solar installa on Installa on of surge protec on devices should follow vendor instruc ons Installa on Procedure WARNING DO NOT CONNECT BDM 300X2 TO THE UTILITY GRID OR ENERGIZE THE AC CIRCUIT S UNTIL YOU HAVE COMPLETED ALL OF THE INSTALLATION PROCEDURES AS DESCRIBED IN THE FOLLOWING SECTIONS Installing the BDM 300X2 Micro inverter System involve...

Page 6: ...of these loca ons using hardware recommended by your module racking vendor Step 3 Connect the BDM 300X2 Wiring Harnesses Each BDM 300X2 comes with one 3 pin bulkhead receptacle mounted on the case The three pins of this connector are for phases L1 L2 and ground This AC connector is oppositely sexed with the connector at the end of the extension cable from the trunk cable through a T connector Plug...

Page 7: ...p you create Complete the connec on map Each BDM 300X2 has a removable serial number label located on the moun ng plate Enter this serial number into the BDG 256 and correspond it to a number in the connec on map Connect the PV Modules Completely install all BDM 300X2 and all system inter wiring connec ons prior to installing the PV modules 1 Mount the PV modules above their corresponding BDM 300X...

Page 8: ...roducing power The LED light is on by 1 second and off by 1 second Orange not communica ng to BDG 256 Green communica ng to BDG 256 Status grounding fault The LED light is in solid red color In case of fault BDM 250 has mul ple protec ve func ons and stops output power The fault message may be sent to a connected BDG 256 gateway through power line communica on The error message is displayed on the ...

Page 9: ...ch micro inverter system to block interference from adjacent other systems 7 If the problem persists please call customer support at NEP WARNING DO NOT ATTEMPT TO REPAIR THE BDM 300X2 IT CONTAINS NO USER SERVICEABLE PARTS IF TROUBLESHOOTING METHODS FAIL PLEASE RETURN THE BDM 300X2 TO YOUR DISTRIBUTOR FOR MAINTENANCE Disconnec ng a BDM 300X2 from the PV Module To ensure the BDM 300X2 is not disconn...

Page 10: ...Display LED LIGHT LED LIGHT Communica ons POWERLINE POWERLINE Dimension D W H mm 277 132 50 277 132 50 Weight Kg 2 9 2 9 Per IEEE 1547A MODEL BDM 300X2 AU D BDM 300X2 EU D INPUT DC Max Recommended PV Power Wp 340 x 2 Vmax PV absolute maximum Vdc 60 PV Input Opera ng Voltage Range Vdc 22 55 Maximum Opera ng PV Input Current Adc 12 x 2 MPPT Tracking Accuracy 99 5 Isc PV absolute maximum Adc 14 x 2 M...

Page 11: ...ogical infesta ons or input voltage that creates opera ng condi ons beyond the maximum or minimum limits listed in the NEP product specifica ons including high input voltage from generators and lightning strikes c the product if repairs have been done to it other than by NEP or its authorized service centers herea er ASCs d the product if it is used as a component part of a product expressly warran...

Page 12: ...or Code s Brief Fault Descrip on and Photos monitoring gateway is required for verifica on Installa on Informa on Modules Used Modules Quan ty Inverters quan ty per string Installa on Company Name Installer Name For the informa on on our warranty terms and condi ons please see our website www northernep com en All fields must be completed in order to process claim Customer Signature Date All rights ...

Page 13: ...12 0011 福岡市博多区博多駅前 3 10 24 藤井ビル 1F TEL 81 092 433 3252 FAX 81 092 433 3171 China Address No 1 Anhe Rd Tsingtao Export Processing Zone Tsingtao China 266113 TEL 86 532 87963900 FAX 86 532 81100917 Email info northernep com Web h p www northernep com h p www nep japan com h p www micro inverter jp ...

Reviews: