background image

WIRING DIAGRAM

PS 1

GROUND

(Factory)

BLACK   - LINE

WHITE   - NEUTRAL

GREEN   - GROUND

VIOLET  - DIM (+)

GREY   - DIM (-)

BLACK

WHITE

GREEN

VIOLET

GREY

TM

Nemalux

I N D U S T R I A L

XR-GEN

rev. A-13

4-14

www.nemalux.com  |   [email protected]  |   Tel 403•242•7475  |   Fax 403•243•6190 

MADE IN CANADA

*Any additional wiring not shown has been capped by the factory and is not to be utilized unless part of supplemental 

instructions for luminaire accessory.

Summary of Contents for XR-GEN Series

Page 1: ...Class 1 Wiring only All supply field wiring must be rated 300V minimum for luminaires with suffix AC 600V minimum for luminaires with suffix HV Ambient Temperature Range XR8 50 C to 75 C XR10 50 C to...

Page 2: ...via retention strap Note Screws are captive fasteners and will remain attached to the cover for ease of reinstall and to prevent loss of fasteners 5 0in 126mm 5 2in 132mm 16 0in 405mm 17 3in 441mm 0...

Page 3: ...0 A for control needs 0 10V Controller must sink current from LED driver 0 10V control connections NOTE To aid in assembly and provide protection against ingress use of a petrolatum or soap thickened...

Page 4: ...REEN VIOLET GREY TM Nemalux I N D U S T R I A L XR GEN rev A 13 4 14 www nemalux com sales nemalux com Tel 403 242 7475 Fax 403 243 6190 MADE IN CANADA Any additional wiring not shown has been capped...

Page 5: ...ead lubricant sealant is necessary Un used conduit opening must be plugged to maintain the integrity of the enclosure STEP 5 Insert and tension M6 set screw to pole to lock rotation STEP 6 Resume inst...

Page 6: ...ly gasket to mount with adhesive backed side Torque to 5 Nm 45 in lbs STEP 5 Install Back Cover Plate with 4x M4 Flat head screws and adhesive backed gasket Apply gasket with adhesive side applied to...

Page 7: ...assembly Torque fasteners to 5 Nm 45 in lbs STEP 5 Thread installed wiring through opening in XR high vibration yoke mount and install XR luminaire into yoke The raised circular bosses on the XR cheek...

Page 8: ...curved slot the luminaire may be configured for an upward or downward adjustable swing STEP 4 Thread installed wiring through openings in yoke mount cheek plate and yoke mount bracket Mount yoke asse...

Page 9: ...ly and provide protection against ingress use of a petrolatum or soap thickened mineral oil based thread lubricant sealant is necessary Un used conduit opening must be plugged to maintain the integrit...

Page 10: ...n through the outer band of the unit and fastening a closed loop Secondary safety hardware must be rated for a minimum of 110lbs Install remaining loop of secondary safety chain or steel cable to suit...

Page 11: ...dy near AC input Secure the surge protector and driver lead wires together as close to the origin of the driver lead wires as possible using the provided zip tie STEP 4 Wire according to wiring instru...

Page 12: ...t conductor and White leads from LED Drivers 3 Connect Green wire from surge protector to splice or terminal connected to Grounding branch circuit conductor and green lead from luminaire case PS 1 GRO...

Page 13: ...provided zip tie STEP 4 Wire according to wiring instructions on Page 12 14 Refer to NEC CEC codes and follow all applicable local standards STEP 5 Close XR Wiring Cover Ensure the retention cable is...

Page 14: ...t conductor and White leads from LED Drivers 3 Connect Green wire from surge protector to splice or terminal connected to Grounding branch circuit conductor and green lead from luminaire case PS 1 GRO...