background image

STEP 1.

Inspect shipping package and contents to ensure no damage has 

occurred during shipping.

STEP 2.

Open XR Wiring Cover with 7mm hex socket driver. Allow Lens to 

hang via retention strap.

NOTE:

Screws are captive fasteners and will remain attached to the Lens for ease 

of reinstall and prevent loss of fasteners. 

STEP 3.

Install provided double-sided tape along side of surge protector and

secure to XR body near AC input. Secure the surge protector

and driver lead wires together as close to the origin of the driver lead

wires as possible using the provided zip tie. 

STEP 4.

Wire according to wiring instructions on Page 12-14.  Refer to 

NEC/CEC codes and follow all applicable local standards.

STEP 5.

Close XR Wiring Cover. Ensure the retention cable is not pinched 

between XR Head and the XR Wiring Cover.  Tighten lens bolts using 

a 7mm socket or box wrench to 1.7 N-m (15 in-lbs).

XR-SP-HV

PART NAME

QTY

1

1

1

BSP3-480-20KA SURGE PROTECTOR

3M VHB TAPE

4" zip tie

XR-SP-HV – SURGE SUPPRESSOR KIT

This XR-SP-HV kit is intended for use with UL Listed 

XR luminaire as marked on the luminaire nameplate.  

Accessory Package Contents

INSTALLATION STEPS

TM

Nemalux

I N D U S T R I A L

XR-GEN

rev. A-13

13-14

www.nemalux.com  |   [email protected]  |   Tel 403•242•7475  |   Fax 403•243•6190 

MADE IN CANADA

SURGE PROTECTOR LOCATION

Summary of Contents for XR-GEN Series

Page 1: ...Class 1 Wiring only All supply field wiring must be rated 300V minimum for luminaires with suffix AC 600V minimum for luminaires with suffix HV Ambient Temperature Range XR8 50 C to 75 C XR10 50 C to...

Page 2: ...via retention strap Note Screws are captive fasteners and will remain attached to the cover for ease of reinstall and to prevent loss of fasteners 5 0in 126mm 5 2in 132mm 16 0in 405mm 17 3in 441mm 0...

Page 3: ...0 A for control needs 0 10V Controller must sink current from LED driver 0 10V control connections NOTE To aid in assembly and provide protection against ingress use of a petrolatum or soap thickened...

Page 4: ...REEN VIOLET GREY TM Nemalux I N D U S T R I A L XR GEN rev A 13 4 14 www nemalux com sales nemalux com Tel 403 242 7475 Fax 403 243 6190 MADE IN CANADA Any additional wiring not shown has been capped...

Page 5: ...ead lubricant sealant is necessary Un used conduit opening must be plugged to maintain the integrity of the enclosure STEP 5 Insert and tension M6 set screw to pole to lock rotation STEP 6 Resume inst...

Page 6: ...ly gasket to mount with adhesive backed side Torque to 5 Nm 45 in lbs STEP 5 Install Back Cover Plate with 4x M4 Flat head screws and adhesive backed gasket Apply gasket with adhesive side applied to...

Page 7: ...assembly Torque fasteners to 5 Nm 45 in lbs STEP 5 Thread installed wiring through opening in XR high vibration yoke mount and install XR luminaire into yoke The raised circular bosses on the XR cheek...

Page 8: ...curved slot the luminaire may be configured for an upward or downward adjustable swing STEP 4 Thread installed wiring through openings in yoke mount cheek plate and yoke mount bracket Mount yoke asse...

Page 9: ...ly and provide protection against ingress use of a petrolatum or soap thickened mineral oil based thread lubricant sealant is necessary Un used conduit opening must be plugged to maintain the integrit...

Page 10: ...n through the outer band of the unit and fastening a closed loop Secondary safety hardware must be rated for a minimum of 110lbs Install remaining loop of secondary safety chain or steel cable to suit...

Page 11: ...dy near AC input Secure the surge protector and driver lead wires together as close to the origin of the driver lead wires as possible using the provided zip tie STEP 4 Wire according to wiring instru...

Page 12: ...t conductor and White leads from LED Drivers 3 Connect Green wire from surge protector to splice or terminal connected to Grounding branch circuit conductor and green lead from luminaire case PS 1 GRO...

Page 13: ...provided zip tie STEP 4 Wire according to wiring instructions on Page 12 14 Refer to NEC CEC codes and follow all applicable local standards STEP 5 Close XR Wiring Cover Ensure the retention cable is...

Page 14: ...t conductor and White leads from LED Drivers 3 Connect Green wire from surge protector to splice or terminal connected to Grounding branch circuit conductor and green lead from luminaire case PS 1 GRO...

Reviews: