21
Close & Trip Rollers and position indication pin
Close and Trip rollers are actuated by the lifter plate on the switchgear floor.
The location indication pin will only fall into the lifter plate slots in the Disconnect and
Connect postions,providing a permissive operation.
For all other locations of the breaker within the cubicle the Citadel must and will be
tripped open and the close function blocked.
Trip roller
Visual indication of Block
the close activation
Close roller
Positive mechanical
permissive
FIGURE 52
FIGURE 53