Citadel 2.0 - Instruction Manual - page:
36
IM
-
C
2.0
-
12
/2
5
/3
0/
4
0/
DO
/F
X
| V
: 1
0 / 1
1 / 2
0
21
Vacuum Interrupters Life Expectation Curve - ANSI C 37.013 breakers
The life expectancy of vacuum interrupters is a function of the number of interruptions
and magnitude of current interrupted.
Breakers must have vacuum interrupter assemblies replaced when they achieve maximum-life
curve limits, when erosion dot is no longer visible or if micro-ohm readings are greater than 100%
above specified nominal.
100.000
63.000
10.000
5.000
1.000
1
10
100
1.000
10.000
Breaking current (rms value) in kA
Rated operating sequences: CO - 30min - CO
Numbers of oper
ating c
ycles
FIGURE: 9
V A C U U M I N T E R R U P T E R / O P E R A T O R