Citadel 2.0 - Instruction Manual - page:
14
IM
-
C
2.0
-
12
/2
5
/3
0/
4
0/
DO
/F
X
| V
: 1
0 / 1
1 / 2
0
21
Note:
Shipments are not released from the NBS factory without a clear bill of lading.
Properly developed methods have been employed for preparation, loading, tarping and
blocking the equipment in the factory, and on the truck before it leaves the NBS factory.
If the equipment is received in a damaged condition, this damage to the equipment
must have occurred while on route and beyond NBS’ control.
Without following procedures as outlined above by the receiving parties, purchaser or
their agent, NBS cannot / will not be held liable for repairs.
NBS will not be held liable for repairs in any case where repair work was attempted
and or performed prior to authorization from NBS.
1.
Remove the shipping carton from the circuit breaker carefully. Keep the shipping
pallets for later possible storage use prior to installation.
2.
Inspect for outward and concealed damage. Notification to carrier must take place
within 15 days to assure any claims resolution.
3.
Each circuit breaker should be lifted propperly. Do not allow any force or crushing
of the side panels of the circuit breaker, or damage to the primary disconnect
(cluster) assemblies.
Refer to Table 2 (page 12) for circuit breaker weights.
4.
Palletized circuit breaker can be moved using a properly rated fork-lift type device.
It is advised that IEEE std C37.20.2 section 9 and Annex are reviewd and incorporated.
Storage
1.
Whenever possible, install the circuit breaker in its switchgear enclosure.
2.
When the circuit breaker is to be placed on a pallet for storage, securely bolt the
breaker to the pallet and cover with strong polyethylene or non-moisture collecting
material.
Indoor storage
Store the circuit breaker indoors in a clean, dry environment that is free of construction
dust, corrosive atmosphere, mechanical abuse and extensive temperature swings.
Outdoor storage
Outdoor storage is not recommended.
Space heating
Space heating must be used to prevent condensation and corrosion. 150 - 250 watts
per circuit breaker of space heating is recommended depending on humidity and
temperature swings.
If the circuit breaker is stored inside the switchgear enclosure- energize the space
heaters if they are available.
R E C E I V I N G , H A N D L I N G A N D S T O R A G E