NI 9144 User Guide and Specifications
|
© National Instruments
|
17
•
UL 60079-0: Ed 5, UL 60079-15: Ed 3
•
CSA 60079-0:2011, CSA 60079-15:2012
Safety Voltages
Connect only voltages that are within these limits.
V terminal to C terminal................................... 30 V max, Measurement Category I
Measurement Category I is for measurements performed on circuits not directly connected to the
electrical distribution system referred to as MAINS voltage. MAINS is a hazardous live
electrical supply system that powers equipment. This category is for measurements of voltages
from specially protected secondary circuits. Such voltage measurements include signal levels,
special equipment, limited-energy parts of equipment, circuits powered by regulated
low-voltage sources, and electronics.
Caution
Do not connect the system to signals or use for measurements within
Measurement Categories II, III, or IV.
Hazardous Locations
U.S. (UL) .......................................................... Class I, Division 2,
Groups A, B, C, D, T4;
Class I, Zone 2,
AEx nA IIC T4
Canada (C-UL) ................................................. Class I, Division 2,
Groups A, B, C, D, T4;
Class I, Zone 2,
Ex nA IIC T4
Europe (DEMKO) ............................................ Ex nA IIC T4 Gc
Environmental
The NI 9144 chassis is intended for indoor use only, but it may be used outdoors if mounted in
a suitably rated enclosure.
Operating temperature
(IEC 60068-2-1, IEC 60068-2-2) ..................... -40 °C to 70 °C
Note
To meet this operating temperature range, follow the guidelines in the
installation instructions for your EtherCAT system.
Storage temperature
(IEC 60068-2-1, IEC 60068-2-2) ..................... -40 °C to 85 °C
Ingress protection ............................................. IP 40
Operating humidity (IEC 60068-2-56) ............. 10 to 90% RH, noncondensing
Storage humidity (IEC 60068-2-56)................. 5 to 95% RH, noncondensing