31
W415-1539 / A / 04.19.16
EN
IMPORTANT:
The LV38 requires a minimum inside enclosure height of 63 1/2" (1613mm), measured
from the bottom of the appliance. For temperature requirements, this area must be left unobstructed. It is
recommended that the enclosure be ventilated at the top and bottom to circulate the hot air.
Before fi nishing in the appliance test the operation using the remote control, cycling it through all
of its different
modes, see “OPERATION” section. Check pressure readings, see “PILOT BURNER
ADJUSTMENT” section.
Once fi nished in, access to the control components can only be done through the
inside of the appliance.
5.4
MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES
!
WARNING
THE FRONT OF THE APPLIANCE MUST BE FINISHED WITH ANY NON-COMBUSTIBLE MATERIALS
SUCH AS BRICK, MARBLE, GRANITE, ETC., AS LONG AS THESE MATERIALS NEVER OVERHANG
INTO THE APPLIANCE OPENING.
63 1/2"
1613mm
MINIMUM
ENCLOSURE
HEIGHT
TOP OF
APPLIANCE
OPENING
26 9/16"
675mm
MINIMUM
25 5/8"
651mm
MINIMUM
COMBUSTIBLE
MATERIAL
NON-COMBUSTIBLE
STEEL STUD FRAME
COMBUSTIBLE
NON-COMBUSTIBLE
TOP OF ENCLOSURE
NOTE: JOINT COMPOUNDS AND TAPES THAT ARE RESILIENT
TO HEAT AND CRACKING SHOULD BE USED WHEN TAPING
AND MUDDING SEAMS.
3"
76mm
0” IF NON-COMBUSTIBLE
FINISHING IS USED SUCH
AS BRICK AND STONE.
3"
76mm
2"
51mm
57"
1448mm
MINIMUM
PLUS RISE**
7" 178mm
TO SIDEWALL
HEAT SHIELD
* Within the appliance enclosure a 6" (152mm) clearance between the top of the vent pipe and combustible
materials is recommended. All other clearances within the enclosure, including where the vent pipe exits the
enclosure are subject to 2" (51mm) to the sides and bottom and 3" (76mm) to the top for horizontal and 1"
(25mm) for vertical.
** See venting section.