144
22 Position Terminal Block
Functions
A.
Provides 6 sets of programmable contacts on
pin 1 thru pin 18 for intersection flash control, remote
alarms, pagers or per user's discretion.
1.
Low Batt: the batteries reach approx
40%
2.
On Batt: the unit is in inverter mode.
3.
Timer: the unit has been in inverter
mode
4.
Alarm: the "Alarm" contact energizes
a. Line Freq error
b. Low O/P watt c. No Temp
d. Overload
f. High Temp
e. No battery connect
g. Low Temp
5.
Fault: the "Fault" contact energizes
when
the following condition appear.
a. Short circuit
b. Batt low voltage
c. Batt high voltage
d. High temperature
e. Overload
B.
Provides 48VDC signal to the PTS on pins 21 & 22
C.
Triggers the self-test by momentarily shorting
Contact Type
Form C dry contacts rated to 1 Amp at 120V
Wiring
Uses 14-26 AWG
Communication Specifications
RS232 / USB Interface
Monitors, controls and calibrates with terminal
emulation software for service personnel to obtain unit diagnostics
RS232
DB-9, Female, Opto-Isolated
Ethernet
Embedded HTML
Note: Specifications subject to change without notice
Summary of Contents for MP Series
Page 3: ...III ...
Page 20: ...20 STEP 1 Connect CONTROL Wires ...
Page 22: ...22 Installation and Troubleshooting Guide Figure 9 ...
Page 30: ...30 MP2000E System Battery Backup System Section 2 Operator s Manual ...
Page 49: ...49 Figure 21 Note See Section 2 2 14 For details on Event Log View under Maintenance submenu ...
Page 51: ...51 2 2 8 Status Submenu CONT D ...
Page 70: ...70 2 3 3 Main Menu ...
Page 72: ...2 3 4 1 RS232 USB Menu Tree ...
Page 74: ...74 ...
Page 104: ...104 Figure 6 70 SMS for Event Log Screen ...
Page 126: ...126 ...
Page 148: ...148 ...