The Controller Setup screen appears after the login. The fields in this screen are
detailed in Figure 6-90. See Figure 6-92 controller setup screen shot.
FIELD
DETAILS
IP Address
Subnet
Mask
Default
Gateway
If not using DHCP, enter data into these fields
Network
Link Speed
The Network link speed is set through a pull-down menu. It is
typically set to “auto” although other available values are:
•
10 full-duplex
•
100 full-duplex
•
10 half-duplex
•
100 half-duplex
DHCP Client
If you have manually entered IP address data, choose “disable”
from the pulldown menu in this field.
Socket Port
of HTTP
Setup
This is the IP socket port number. Port 80 is the standard ( TCP )
socket port number for hyper text transfer protocol ( HTTP ). Other
values are “81” and “disabled.”
Socket Port
of Serial I / O
The Default is 100
— make the number correspond to the terminal
emulator ( HyperTerminal ) serial I / O setting or Myers MEMS serial
I / O setting. Configure the card for TCP server.
Destination
IP Address /
Socket Port
( TCP Client
and UDP )
Connection
These settings correspond to the “TCP Client” and “UDP”
selection in “Socket port of serial I/O.”
Refer to the Hyperterminal Example in Figure 6-113.
TCP Socket
Inactive
Timeout
( in minutes
)
The default is 10 minutes.
Serial I / O
Settings
With the Ethernet-to-serial adapter card installed in the MP2000E,
leave these settings unchanged. These are the RS232
Communication settings between the Ethernet card and the
MP2000E.
Interface of
Serial I / O
Packet Mode
of Serial
Input
Setup
Password
This allows the Controller Setup access password to be changed.
The default is 1111.
Figure 6-90: Controller Setup Screen Fields
Summary of Contents for MP Series
Page 3: ...III ...
Page 20: ...20 STEP 1 Connect CONTROL Wires ...
Page 22: ...22 Installation and Troubleshooting Guide Figure 9 ...
Page 30: ...30 MP2000E System Battery Backup System Section 2 Operator s Manual ...
Page 49: ...49 Figure 21 Note See Section 2 2 14 For details on Event Log View under Maintenance submenu ...
Page 51: ...51 2 2 8 Status Submenu CONT D ...
Page 70: ...70 2 3 3 Main Menu ...
Page 72: ...2 3 4 1 RS232 USB Menu Tree ...
Page 74: ...74 ...
Page 104: ...104 Figure 6 70 SMS for Event Log Screen ...
Page 126: ...126 ...
Page 148: ...148 ...