135
Figure 53
Line Mode Waveform
Figure 53 is a waveform illustrating normal waveforms during line mode. The top trace is
the line output of the PTS with respect to neutral and the lower trace is the line input of the
utility with respect to the neutral. The utility line is 118VAC, 60Hz which is within the
normal specification for the MP2000E. The exact transfer set points are adjustable by the
parameters in the line detection area of the menu. For further details, refer to the
Adjustments section of the manual, under Line Detection Adjustments.