Chapter 2 Compressor Specifications and Configuration
Screw Compressor i-series
2.3
Compressor Specifications
2-4
2.3.3 Alarm Set Values
To protect the compressor, please set the alarm shown in the table below.
Table 2-3 Application Limits of i-series Compressor *
Note 1
Item
Unit
Alarm
Stop
Rotation speed
min
-1
High
—
i125S, i160S: 4550 (0 sec.)
i125L, i160M, i160L: 3650 (0 sec.)
Low
—
1450 (0 sec.)
Discharge pressure
MPa
High
1.9 (0 sec.)
2.0 (0 sec.)
Low
—
—
Suction pressure
MPa
High
0.6 (30 sec.)
0.6 (60 sec.)
Low
-0.05 (30 sec.)
-0.05 (60 sec.)
Differential pressure for
lubrication
(Po - Ps) *
Note 2
MPa
High
—
—
Low
0.6 (30 sec.)
0.5 (30 sec.) *
Note 3
Discharge temperature
°
C
High
90 (5 sec.)
95 (0 sec.)
Low
—
—
Suction temperature
°
C
High
60 (60 sec.)
—
Low
-58 (30 sec.)
-60 (30 sec.)
Discharge superheat
°
C
High
—
—
Low
15 (60 sec.)
10 (60 sec.)
Suction superheat
°
C
High
—
—
Low
0 (30 sec.)
0 (60 sec.)
Lubrication temperature
°
C
High
80 (60 sec.)
85 (60 sec.)
Low
30 (60 sec.)
25 (60 sec.)
Unless otherwise noted, the pressure unit MPa represents the gauge pressure in this manual.
*
Note 1:
The values in the parentheses are the maximum operation delay times.
The values have been set to protect the compressor.
*Note 2:
Po = Oil supply pressure, Ps = Suction pressure
*
Note 3:
This alarm stop is set for normal operation. At the time of the start-up of the compressor,
it is not necessary to perform this alarm monitoring after start until 300 seconds.