3. Edit the parameters.
o
Capacity: Enter the fan capacity.
o
KWh: This field displays the amount of kilowatts used. Read-only.
o
Operation: Select if the relay is normally open or normally close.
4. Click Save.
7.3.1.2
0 – 10 Volt Fans
1. On the Device and Sensors screen, click a fan analog output port.
2. Click
.
3. Edit the parameters.
o
Minimum/Maximum Voltage: Enter the minimal and maximal voltage used to calibrate
the fan speed. For example, if the minimum voltage is set to 2V and the maximum to 8V
the controller applies the calculated 0-100% output over a 2V-8V signal.
o
Capacity: Enter the fan capacity.
o
KWh: This field displays the amount of kilowatts used. Read-only.
o
Boost Time: During this amount of time, the controller applied full power to the fan motor
(100%).
4. Click Save.
5. To test in the minimal and maximum voltages, click Test.
Summary of Contents for Rotem Trio 20
Page 20: ... Munters AB 2020 20 Figure 6 Relay and port numbering ...
Page 44: ... Munters AB 2020 44 ...
Page 99: ... Munters AB 2020 99 Refer to Tunnel Ventilation page 123 for more details ...
Page 141: ... Munters AB 2020 141 If an outside temperature sensor is enabled map timers to it if required ...
Page 160: ... Munters AB 2020 160 23 3 2TRIO 20 CONTAINER SPARE PARTS ...
Page 162: ... Munters AB 2020 162 23 3 3TRIO 20 DOOR CARDS SPARE PARTS ...
Page 164: ... Munters AB 2020 164 23 3 4TRIO 20 MAIN CONTAINER SPARE PARTS ...
Page 186: ... Munters AB 2020 186 Figure 33 Relay and port numbering 26 2 3POWER Figure 34 Power ports ...
Page 199: ... Munters AB 2020 199 2 Insert and secure the SMA connector ...
Page 202: ... Munters AB 2020 202 example only ...