12.3
Measuring Fan
Measuring fans measure the air speed inside the rooms. More exactly, the fan is used to precisely
determine the actual conveyed exhaust air volume. This device can be used for:
•
Measuring real time air speed
•
Enable ventilation compensation if the air speed does not meet the calculated minimum ventilation
requirements.
Define a sensor as Measuring Fan. Refer to Mapping Devices, page 48.
12.3.1
M
EASURING REAL TIME AIR SPEED
In this setup, the measuring fan is used to show the real time air speed.
1. Go to System > Devices & Sensor. On the Measuring Fan port:
a. Define the Related Fan as None.
b. Verify that the measuring fan is enabled.
2. Go to System > Control Strategy > Ventilation
.
3. In the Measuring Fan Usage parameter, define the usage as Monitor.
NOTE
The Measuring Fan Maximum Compensation parameter is irrelevant in this setup.
12.3.2
V
ENTILATION
C
OMPENSATION
In this option, the measuring fan is used to ensure that the air volume meets the minimum defined in the
Minimum and Maximum Ventilation, page 100. The Minimum Ventilation function defines the minimum
amount of air that the fans must supply. The Measuring Fan measures the actual amount of air supplied. If
the actual amount is less than the required amount of air, the Measuring Fan increases the speed of a
designated fan to compensate for the difference.
Define a sensor as Measuring Fan. Refer to Mapping Devices, page 48.
Summary of Contents for Rotem Trio 20
Page 20: ... Munters AB 2020 20 Figure 6 Relay and port numbering ...
Page 44: ... Munters AB 2020 44 ...
Page 99: ... Munters AB 2020 99 Refer to Tunnel Ventilation page 123 for more details ...
Page 141: ... Munters AB 2020 141 If an outside temperature sensor is enabled map timers to it if required ...
Page 160: ... Munters AB 2020 160 23 3 2TRIO 20 CONTAINER SPARE PARTS ...
Page 162: ... Munters AB 2020 162 23 3 3TRIO 20 DOOR CARDS SPARE PARTS ...
Page 164: ... Munters AB 2020 164 23 3 4TRIO 20 MAIN CONTAINER SPARE PARTS ...
Page 186: ... Munters AB 2020 186 Figure 33 Relay and port numbering 26 2 3POWER Figure 34 Power ports ...
Page 199: ... Munters AB 2020 199 2 Insert and secure the SMA connector ...
Page 202: ... Munters AB 2020 202 example only ...