MCS300
10 Technical specification
Technical data MCS300
230V/50 Hz
115V/50 Hz
115V/60 Hz
Process air
(1)
System airflow (m³/h)
330
330
330
Nominal airflow with ducting (m³/h)
300
300
300
Minimum available static pressure (Pa)
200
200
200
Reactivation air
(1)
Nominal airflow with ducting (m³/h)
60
47
60
Minimum available static pressure (Pa)
200
200
250
Fan motor
Motor, power (kW)
0,15
0,15
0,15
Motor, current (A, 1 ~)
1,05
2,1
2,1
Drive motor
Motor, power (kW)
0,002
0,002
0,002
Motor, current (A, 1 ~)
-
-
.-
Reactivation heater
Reactivation heater, power (kW)
2,0
1,5
1,5
Temperature increase (°C)
95
73
73
Electrical power and nominal current (kW)
Maximum electrical power (kW)
2,2
1,7
1,7
Filter
Filter kit (Article No.)
130025/1 KIT
130025/1 KIT
130025/1 KIT
Temperature range
Permitted ambient operating temperature
-20 to +40 °C
-20 to +40 °C
-20 to +40 °C
Other data
Protection form
IP44
IP44
IP44
Fan motor winding insulation class
F
F
F
Maximum sound level without ducting (dBA)
Max. 60,0
Max. 60,0
Max. 60,0
Total unit weight (kg)
25
25
25
Rotor type
HPS
HPS
HPS
Dimensions
Depth (mm)
400
400
400
Width (mm)
400
400
400
Height (mm)
550
550
550
1)
The specified figures are nominal values based on inlet temperatures at the fans of 20 °C and an air density of 1,2 kg/m
3
.
Table 10.1 Technical specification
190TEN-1027- F1404
Technical specification