MCS300
3.10 Connecting the humidistat
3.10.1 General
The connection socket for the humidistat is located in the storage compartment for the power
cable, see
. The appropriate plug for the humidistat is delivered with the unit, see section
3.10.2, Humidistat connection kit
. The humidistat shall be mounted 1–1.5 m. above the floor and positioned so
that it is not exposed directly to dry air from the unit or incoming moist air from opening and closing doors.
It should not be placed close to a heat source, or so that it is exposed to direct sunlight. The humidistat shall
be a single stage humidistat and connected so that the controlling circuit closes as relative humidity increases.
The connecting cable shall be screened and have copper conductors with a minimum cross-section area
of 2 x 0.75 mm
2
.
0 1
A
Figure 3.4 Connection socket for humidistat (A)
190TEN-1027- F1404
Installation
10