4.3.2 Manual operation
1. Reset measurement of power consumption as required, see section
.
2. Switch the on-off switch to position I, see
3. Select the
Man
operating mode by pressing the operating mode selector button.
4.3.3 Automatic operation
For the dehumidifier to operate in
Auto 1
or
2,
the humidistat must be connected to the humidistat socket of
the unit, see section
3.10, Connecting the humidistat
.
1. Reset measurement of power consumption as required, see section
.
2. Adjust the humidistat to the desired setpoint.
3. Switch the on-off switch to position I, see
4. Select the
Auto 1
or
2
operating mode by pressing the operating mode selector button, see
NOTE!
Connection of the humidistat activates a built-in 2 minutes delay function for re-start. The opening and
closing of the humidistat circuit within the 2 minutes period will not start the dehumidifier again because of the delay
function. In case the humidistat circuit has been opened for more than 2 minutes and then closes, the dehumidifier
will start immediately. The purpose with this function is to prevent the circuit from continuously cycling on and off, in
case the humidistat is installed in a poorly choosen location.
4.4 Stop
Switch the on-off switch to position
0
, see
.
4.5 Adjusting reactivation temperature
If a damper is installed on the wet air side, the dehumidifier’s reactivation temperature is adjusted as follows:
1. While the unit is operating, press the measurement selector so the reactivation temperature is shown
on the display, see
2. Adjust the damper and check the reactivation temperature. When the damper is properly adjusted, the
difference between the reactivation temperature and the ambient temperature should be about 95 °C.
NOTE!
At start-up, the display shows LO °C for reactivation temperatures below 65 °C.
4.6 Fault indication
Excessively high reactivation temperatures are indicated on the control panel, see
-
Fixed light, the dehumidifier is still running.
-
Blinking light, the dehumidifier has stopped.
Man
Auto 1
Auto 2
KWH
Temp
E
Figure 4.3 Fault indication
E. Indication for temperature control and tripped thermostat
190TEN-1027- F1404