Munters Farm P-XL User Manual Download Page 30

 

© Munters AB, 2015 

30 

 

Warm Temperature – Difference Below Heat: Differential below the heat temperature (refer 
to Temperature Curve, page 15) that defines outside temperature as Warm in the Soft 
Min/Max table.  For example, if the Heat Temperature is 78° F, Warm Temp. – Diff Below 
Heat is 2.0, than the outside temperature is defined as warm at 76° F. 

 

Cold Temperature: Outside temperature (or below) at which Air per Kg/Lb. (Cold) capacity is 
reached.  

When the outside temperature is between the Warm and Cold Temperature, the flow rate is 
calculated at a proportional rate. 

 

Air Change: As the temperature rises from the Cold Temperature parameter to the Heat 
Temperature (or drops from the Heat Temperature to the Cold Temperature parameter), the 
minimal air volume rises/falls proportionally.  Air Change defines the minimal change in air 
temperature that must takes place to cause a change in the air supply.    

 

Fan Cycle Time: The total amount of time that the fans operate while operating under Minimum 

Ventilation. During this time, the fans supply the required volume of air at the minimum 
ventilation level required.  Farm Premium adjusts the minimum ON time and OFF time as 
needed. If the fans cannot supply the required volume at a particular level of ventilation, Farm 
Premium automatically adjusts the minimum ventilation level. 

o

 

Minimum ON Time in Vent Cycle: The minimum amount of time that the fans operate 
during a cycle. Farm Premium adjusts the actual fan time as needed. 

o

 

Minimum OFF Time in Vent Cycle: The minimum amount of time that the fans do not 
operate during a cycle. Farm Premium adjusts the actual fan time as needed. 

As the temperature rises, the actual Minimum OFF Time decreases until it reaches the minimum time; 
only then does the Minimum On Time begin to rise.   

NOTE:

 

If the temperature goes above the Band Temperature, Power Ventilation begins and times are 
adjusted accordingly.  

 

Air Change By Humidity/CO2%: As the humidity/CO2 levels rise above the levels specified 
in Humidity Treatment and CO2 Treatment, the minimal air volume rises proportionally.  Air 
Change By Humidity/CO2% defines the minimal change in in these levels that must take place 
to cause an increase in the air supply. 

 

Air Per Weight Curve Mode: By default, Air per Kilo/Lb. has two data points: cold 
temperature and warm.  If desired, the user can add an additional intermediate data point 
which is between the two default points. This point determines the quantity of air to be 
distributed when the temperature reaches the midpoint between the cold and warm 
temperatures. 

 

SOFT MIN/MAX LEVEL BY WEIGHT (OUT TEMP) 

Day 

Min 

Level 

Air Per Kg/Lb 

 

Max  

Level 

 

 

Cold 

 

Warm 

 

10 

12 

15 

17 

19 

21 

35 

0.5 

0.5 

0.5 

1.1 

1.1 

1.1 

1.1 

1.1 

1.1 

0.9 

0.9 

0.9 

1.4 

1.4 

1.4 

1.4 

1.4 

1.4 

1.4 

1.5 

1.5 

1.5 

1.7 

1.7 

1.7 

1.7 

1.7 

1.7 

1.7 

16 

16 

16 

16 

21 

21 

21 

21 

21 

22 

 

Summary of Contents for Farm P-XL

Page 1: ...User Manual Farm Premium Premium P Premium XL P XL Climate Controllers for Poultry and Pigs Ag MIS UmGB 2224 01 15 Rev 1 7 P N 110476 Farm Premium Controllers ...

Page 2: ...he attached technical documentation This document is destined for the user of the apparatus it may not be reproduced in whole or in part committed to computer memory as a file or delivered to third parties without the prior authorization of the assembler of the system Munters reserves the right to effect modifications to the apparatus in accordance with technical and legal developments ...

Page 3: ...Variable Heater Help Set Definitions 19 3 1 5 Variable Floor Heater Set Definitions 22 3 2 Introduction to Humidity Ammonia and CO2 Treatment 23 3 3 Humidity Treatment 24 3 3 1 Humidity Treatment Help Set Definitions 24 3 4 CO2 Treatment 25 3 4 1 CO2 Treatment Help Set Definitions 26 3 5 Min Max Level 26 3 5 1 By Day and By Soft Days Curve 27 3 5 2 By Time 27 3 5 3 Day Soft Min 28 3 5 4 By Weight ...

Page 4: ...2 4 9 2 Control via Quantity 52 4 9 3 Water and Feed Help Set Definitions 53 4 10 Extra Systems 54 4 11 Emergency Setting 54 4 11 1 Emergency Setting Help Set Definitions 55 4 12 Water on Demand 56 4 12 1 Relay Control 56 4 12 2 Sensor Control 57 4 12 3 Water on Demand Help Set Definitions 57 4 13 Natural Program 58 4 13 1 How Does Natural Ventilation Work 58 4 13 2 Preliminary Steps 59 4 13 3 Def...

Page 5: ...erature Curve Set Definitions 76 6 SCALE MENU 77 6 1 Scale Layout 77 6 2 General Settings 78 6 2 1 General Settings Help Set Definitions 78 6 3 Bird Scale Setting 79 6 4 Silo Setting 79 6 5 Bird Curve 80 6 5 1 Bird Curve Help Set Definitions 80 6 6 History 80 6 7 Feed Conversion 81 6 8 Test 82 6 9 Calibration 82 6 9 1 Scale Calibration 82 6 9 2 Silo Calibration 83 6 10 Silo Auger Layout 84 7 HISTO...

Page 6: ... Sensor Calibration 97 9 6 Feed Calibration 98 9 7 Water Calibration 98 9 8 Ventilation Potentiometer Calibration 98 9 9 Nipple Flushing 99 9 9 1 Nipple Flushing Help Set Definitions 99 9 10 Feeders Drinkers 100 9 10 1 Feeders Drinkers Help Set Definitions 100 9 11 Save Settings 101 9 11 1 Saving to a Data Plug 101 9 11 2 Saving to an SD Card 101 9 12 Load Settings 102 9 12 1 Loading from a Data P...

Page 7: ...g Wind Direction 113 10 6 4 Stop Fans 113 10 6 5 Vent Curtain Help Set Definitions 113 10 7 Temperature Definition 114 10 8 Fan Air Capacity 115 10 9 House Dimensions 115 10 10 Communication 116 11 APPENDIX A OUTPUT DATA 117 12 APPENDIX B FARM PREMIUM LAYERS 120 12 1 Layers Main Screen 120 12 2 Layers Vent and Curtain Levels 121 12 2 1 Layer Inlet Control 121 12 2 2 Layer Vent Curtain Inlet levels...

Page 8: ...1 2 Introduction Congratulations on your excellent choice of purchasing a Farm Premium Controller In order to realize the full benefit from this product it is important that it is installed commissioned and operated correctly Before installation or using the fan this manual should be studied carefully It is also recommended that it is kept safely for future reference The manual is intended as a re...

Page 9: ...ments The Farm Premium precisely coordinates ventilation levels providing the optimal amount of fresh air balanced with heating costs The light and feed clocks enable efficient feed distribution Besides advanced cooling pad methods you benefit from superior stir fan programs to recover ceiling heat and other features Taken together Precision Mode s numerous features enable significant profitabilit...

Page 10: ... Back key Access help screens and graphs Erase typing mistakes Enter menus values open windows Scroll up down left and right Enter values select options and make selections Toggle between positive and negative values and mark check boxes 2 1 2 RELAY SWITCHES Figure 2 Standard Relay Switches Figure 2 illustrates a row of standard relay switches Set each relay to On Always on Off Always off ...

Page 11: ...eys when the controller displays the Main Screen Software version Return to standard main screen Temperature humidity status and wind chill temperature NOTE If two humidity sensors are installed Hot Screen 2 displays their average Curve status Curtain tunnel vent and attic opening positions Bird Scale Natural Program Status Refer to Natural Program Hot Screen page 61 Light status Analog output sta...

Page 12: ...the operating mode NOTE When in Layer Mode refer to Layers Main Screen page 120 1 Sensors Displays individual sensor readings Temperature sensors marked with dark squares form the current average temperature o Filled square Indicates the sensor participates in the average calculation o Empty square Indicates the sensor does not participate in the average calculation SENSORS AV TEMP ACTIVE Temp1 37...

Page 13: ... outputs that are off 4 Status Provides important general information such as the time and ventilation mode EXAMPLE NOTE Go to Table 1 Sensor Readings page 117 to view all the available readings 5 Messages Displays important messages alarms The title bar displays the number of important messages and if there are several messages they each appear in turn SENSORS Temp1 37 9 Temp2 16 2 Temp3 28 2 E T...

Page 14: ...re feed water read save to plug 8 Install sensors devices communication etc 2 2 Selecting the Mode Farm Premium runs in four modes Broiler Layer Breeders and Pigs To select the mode 1 Disconnect the power cable from the power source 2 Reapply power while pressing Delete The Cold Start screen appears 3 Select Yes The Choose Controller Type appears 4 Select the required mode 5 Press Enter NOTE The m...

Page 15: ...If a zone does not have an assigned sensors calculations are based on the current average temperature 4 In Control Temperature Curve define the required target temperature curve o Set up to 20 lines 999 growth days When a curve is not required for example when growing layers enter temperatures in the first line only o Define Day Set the growth day You can program negative growth days up to 2 for p...

Page 16: ...special circumstances The curve appears in the Status Window and you can use the ENTER and Up or ENTER and Down hot key combinations to change the offset Set Temp Change Reminder Diff Sets the change in set temperature that triggers a reminder for you to set backup thermostats Often producers forget to set backup thermostats as their birds grow from baby chicks to market age so the Farm Premiumrem...

Page 17: ...erature Putting this parameter at 0º sets the non brood areas to the heater temperature 3 1 2 RADIANT HEATERS HELP SET DEFINITIONS To configure the radiant heaters 1 In Installation Relay Layout define at least one relay as a radiant heater page 107 2 Configure the following parameters o Radiant Low Differential from Heat Set Set degree of difference from Heat for LOW Radiant Heaters to begin work...

Page 18: ...ventilation system during minimum ventilation cycles using heaters and fans connected to relays When enabled heaters operate during the fans cycle off time as defined in the Levels of Ventilation Cycle Timer On and Off parameters How does it work Between the Heat Temperature and the differential temperature heaters do not operate When the temperature goes below the Heat Off temperature minus the L...

Page 19: ...EFINITIONS The Farm Premium Controller enables configuring up to eight variable heaters The heater output changes according to the output of a 0 10 VDC device Install at least one analog output card To configure the variable heaters 1 In Installation Analog Output configure a up to eight analog outputs as variable heaters b the minimum and maximum voltage output for each heater 2 In Control Contro...

Page 20: ...fferential is 8 o If the temperature is between 77 to 78 the output voltage is the minimum voltage defined in Installation Analog Output 1 volt in this example o If the temperature continues to drop the output voltate increases until it reaches the maximum voltage defined in Installation Analog Output Output increases or decreases to keep the temperature within the Target Temperature and Heat Off ...

Page 21: ...rence Below Heat High Difference Below Heat Temperature at which the heater begins to operate at maximum output o Response Time seconds Amount of time before the controller begins to change the ventilation 3 1 4 3 Linear Valve Linear Valve enables defining that variable heater input voltage is always equal to or above the minimum input defined in Installation Analog Sensors When the Analog Heat Mo...

Page 22: ...nable configuring up to two variable floor heaters The output of the heaters changes as the temperature increases or decreases Install at least one analog output card To configure the variable floor heaters 1 In Installation Analog Output configure a up to two analog outputs as variable heaters b the minimum and maximum voltage output for each heater SYSTEM PARAMETERS RADIANT HEATERS Rad Low Diff ...

Page 23: ...crease in ventilation level Increase in air weight The total amount of air that fans need to provide increases by a user defined amount Fan stay on until CO2 humidity or ammonia levels fall to their defined levels This option is only available when using Minimum Ventilation by Weight Humidity treatment by heat In cold air situations heaters can be turned on to lower the relative humidity If there ...

Page 24: ... Duration Seconds Number of seconds the controller maintains the increased level of ventilation 4 Set the Humidity Sensor Alarm page 72 3 3 1 HUMIDITY TREATMENT HELP SET DEFINITIONS While viewing the Humidity Treatment menu Press HELP select SET and press ENTER Humidity Band Hysteresis band for Humidity Treatment Humidity Treatment below Heat Select YES or NO for allowing Humidity Treatment when h...

Page 25: ...s an outside temperature sensor refer to Temperature Definition page Error Bookmark not defined NOTE If the heaters are operating because of the interior temperature Humidity Treatment by Heater is disabled NOTE Broiler and Breeder Modes support Humidity Treatment by Heaters 3 4 CO2 Treatment CO2 treatment forces an increase in ventilation level when the CO2 level is too high It holds the increase...

Page 26: ... number key to select the fan o Tunnel Designate a specific tunnel press a number key to select the fan o None Disables the treatment To enable the exhaust tunnel options in Installation Relay Outlet or Installation Analog Output designate a relay variable device as a tunnel or exhaust fan CO2 Treatment by Heaters This parameter enables running the heaters in situations where the CO2 level is high...

Page 27: ...Days Curve o By Time o Day Soft Min o By Weight 3 5 1 BY DAY AND BY SOFT DAYS CURVE Day Set growth day Min Set minimum ventilation level for controller Max Set maximum ventilation level for controller NOTE BY DAYS CURVE generates an incremental increase decrease between the defined days BY DAYS operates according to the min max values of the day s min max values until the following day defined is ...

Page 28: ...temperature rises to the heat setting This means inside and attic soft min vent choices to latch to the lowest level reached as long as the temperature remains below the heat setting 3 5 4 BY WEIGHT NOTE Only Broilers and Layers mode supports Minimum Ventilation By Weight The By Weight option enables controlling the minimum air flow depending on the number of birds their weight and the current out...

Page 29: ...es between days for example between day 6 and day 10 in the screen above the air volume rises proportionally each day once a day For example on Day 7 the Cold Air per Kg Lb rises to 0 65 on Day 8 0 8 and so on o Maximum Level Set the maximum level of ventilation refer to Levels of Ventilation page 38 8 In Management Bird Inventory type the number of birds 9 In the Help menu define the parameters a...

Page 30: ...el o Minimum ON Time in Vent Cycle The minimum amount of time that the fans operate during a cycle Farm Premium adjusts the actual fan time as needed o Minimum OFF Time in Vent Cycle The minimum amount of time that the fans do not operate during a cycle Farm Premium adjusts the actual fan time as needed As the temperature rises the actual Minimum OFF Time decreases until it reaches the minimum tim...

Page 31: ...e minimum required level Farm Premium displays an alarm Below Min Air Cycle On Off Displays the current minimum and maximum fan on and off times Total Air M3 h Displays the current minimum and maximum quantity of ventilation per hour Air WGT Displays the current amount of ventilation per kilo pound of bird weight 3 6 Static Pressure Set target parameters for Static Pressure at High and Low Outside...

Page 32: ...Low Static Pressure Alarm Set alarm for low static pressure High Static Pressure Alarm Set alarm for high static pressure Static Pressure Band Set required band for pressure in tunnel ventilation mode Attic Target Static Pressure Set required static pressure when in attic mode Static Pressure Band Set required band for attic ventilation mode 3 6 1 DISABLING THE STATIC PRESSURE SENSOR To disable th...

Page 33: ...troller ignores low static pressure alarms while in tunnel mode Time to Produce Static Pressure seconds Enter the length of time to reach target pressure when minimum ventilation fan cycle is on Attic Advance Opening Time seconds Define the amount of time for the attic inlets to open before minimum vent cycling fans turn on 3 6 3 MULTI STAGE TUNNEL CURTAINS When in static pressure mode and employi...

Page 34: ...ntrol method By Days By Days Curve By Time By Soft Min and Weight Refer to Min Max Level page 26 for more details Heat Cycle Enable cycle heaters Refer to Cycle Heaters Set Definitions page 18 Analog Heat Mode Define the variable heating mode Linear Proportional Linear Valve Refer to Variable Heater Help Set Definitions page Error Bookmark not defined 3 8 System Parameters System Parameters consol...

Page 35: ...ment the ammonia level drops below the Stop Value parameter the ventilation level automatically returns to that level used before ammonia treatment began This function requires an ammonia sensor 1 In Install Analog Sensors refer to Analog Sensors designate one sensor as an ammonia sensor 2 If required go to Service Ammonia and calibrate the sensors refer to Ammonia Calibration 3 In Control Ammonia...

Page 36: ...nt when heaters are operating set in Temperature Curve o Ammonia Treatment By This parameter designates the method used when ammonia treatment begins Normally this parameter is relevant only when minimum ventilation is running When a treatment is required select the method to be employed Level Increases the ventilation level when a treatment is required NOTE When employing Ventilation by Weight th...

Page 37: ...ues bias the Farm Premium slightly toward warmer temperatures as would be appropriate for young birds The level increase delay is longer than the level decrease delay You may wish to reverse these values by the time you have market age broilers since they are more sensitive to heat stress than to cold Although many of the levels have 0 0 differential temperatures certain levels should have differe...

Page 38: ...factorily with factory default settings 1 Do one or both o In Install Relay Outlet refer to page 107 define at least one relay as a Tunnel Fan or Exhaust Fan o In Install Analog Output refer to page 110 define one function as Tunnel Fan or Exhaust Fan 2 In Device Setting Levels of Ventilation configure the parameters as required 3 Configure the Help Set parameters as required DEVICE SETTING 1 LEVE...

Page 39: ...thing other than 0 and the controller calculates the Cycle timer OFF automatically Exhaust Control exhaust fans according to Continuous Cycle and Rotate Tunnel Control tunnel fans according to Continuous Cycle and Rotate Air Capacity Displays the current exhaust fan or tunnel air flow for each ventilation level If Variable Speed Fan Levels have been set refer to page 41 the speed percentage is tak...

Page 40: ...Premium determines the calculated temperature actual temperature wind chill temperature and uses this temperature When calculating the Tunnel Mode level up down algorithms When operating the Cool Pad if enabled in System Variables refer to Operate Cool Pad page 40 NOTE The Wind Chill factor influences controller operation from the 1st tunnel level The actual temperature 1 determines the entry and ...

Page 41: ...he operating mode determines the curtain control procedure NOTE Users employing Layers Mode refer to Layers Vent and Curtain Levels page 121 NOTE Before setting the levels define the opening mechanism refer to Vent Curtain Setup page 111 1 In Install Relay Outlet refer to page 107 define at least one relay as Curtain Open Tunnel Open Vent Open or Attic Open 2 If your installation includes curtains...

Page 42: ...et the day the second vent begins operating Default 1 NOTE You can set negative days 1st Level for 2nd Vent to Operate Set the level the second vent begins operating Default 1 Attic Minimum Attic Temperature To Operate Set the minimum temperature to activate the Attic operation Operate Until Day Set the last day for attic operation broilers only Operate From To Time Set the time frame for attic op...

Page 43: ...110 NOTE The numbers shown in the screen under Variable Fan depend on how you defined the fans in Installation Relay Layout and Analog Output NOTE T means the level is in tunnel mode Ventilation Level Read only Variable Fan Set variable speed fan operation in percentages Stir Fan Number Control stir fans according to Continuous Cycle On Cycle Off ventilation cycles are the same as previously set i...

Page 44: ...ilation air for buildings having stir fans to mix the air coming in with warm inside air C D E sensors diff temperature These options create three stir fan groups which operate according to sensor differentials 4 5 1 STIR FAN PROGRAM HELP SET DEFINITIONS While viewing the Stir Fan Program menu Press HELP select SET and press ENTER STIR FAN PROGRAM Fan P R O G R A M No A B C D E 1 2 3 4 5 6 7 8 SYS...

Page 45: ... in seconds for the stir fans to operate From To Level Limit the program to operate between the levels defined From To Time Define the time frame for the program to operate 24 hour format Program C D E Sensors Diff Temp or Independent Temp Diff to Operate Set the degree of difference between sensors for stir fans to begin operating NOTE If this parameter is set to 0 zero the variable stir fan runs...

Page 46: ...tings To Humidity Set maximum humidity allowed before stopping cool pad You can enter 100 On Sec Set the maximum on time for each cycle of cool pad operation Off Sec Set the minimum off time for each cycle of cool pad operation 4 6 1 COOL PAD HELP SET DEFINITIONS While viewing the Cool Pad menu Press HELP select SET and press ENTER Temperature Band Define the on off hysteresis relative to temperat...

Page 47: ... Sensor 2 2 0 82 Cool Pad Minimum Level In systems having more than one pump this parameter enables keeping a cool pad inoperative until the associated tunnel curtain turns on Define the minimum level for each cool pad NOTE When the Difference Between Cool Pads Stage is enabled the cool pads operate according to both conditions Cool Pad Flush Flush Cool Pad At Set time of day hh mm to start contin...

Page 48: ...to Enable Operation Set the maximum ventilation level for fogger operation Enable Rotation Enable this function to use a different fogger relay each cycle This function enables dispersing the droplets at a higher pressure to wet the animal NOTE Munters recommends keeping this function set at the default setting No Difference between Foggers Stage Farm Premium supports four fogging stages The contr...

Page 49: ...6 Days or Week the screen below appears 1 Select Feed and press Enter The Light parameters screen appears These parameters configure the Light functions on feed days 2 Configure the parameters 3 Select No Feed and press Enter The Light parameters screen appears These parameters configure the Light functions on non feed days 4 Configure the parameters Day Set Growth Day In the example the brood lig...

Page 50: ...ed for the light intensity to rise from 0 to the designated level Sunset Time minutes The amount of time required for the light intensity to decline from the designated level to 0 Allow Spiking from Day The day spiking begins Spike Cycle minutes The time length that the spike is at its maximum level Reaching the maximum level and returning to the preset level both take one minute For example if th...

Page 51: ...libration page 97 for details Figure 6 Lighting without Spiking Figure 7 Lighting with Spiking NOTE The initial reference time for the Spike Cycle is the end of Sunrise The spike begins Spike Duration minutes before the end of the Spike Cycle and has one minute up and down ramps in intensity If Sunrise Duration is set to zero no spiking occurs 4 9 Water Feed This menu sets the operating conditions...

Page 52: ...le Menu Scale Layout page 77 map each silo to a channel 3 In Device Settings Water Feed Help Settings enable Feed by Quantity 4 In Device Water and Feed define the parameters as required 5 Set the Water Overflow Alarms and Water Shortage Alarms page 71 Day Set growth day You can define days as negative days Enter the number and then press the key Growth days stay at the defined parameters until th...

Page 53: ...WATER AND FEED HELP SET DEFINITIONS These parameters define the feed and water delivery schedule through the week NOTE The Water and Feed parameters work in conjunction with the Lighting parameters Feed Day Cycle o Daily Same schedule for every day of the week o 2 6 Days Select a cycle that lasts the number of days chosen and then repeats itself For example 2 Days means that the cycle lasts two da...

Page 54: ...te Off sec Off time for Extra System after completion of on time If you have values in both ON and Off the extra system cycles If you have zero OFF time and any ON time the system simply stays on as long as the other parameters are satisfied NOTE All parameters must be satisfied for an Extra System to operate For example if the temperature is below the From Temperature or the Humidity below the Fr...

Page 55: ...d to temperature during Operate Choose whether the Minimum Vent timer applies to this device or only the temperature differential 4 11 1EMERGENCY SETTING HELP SET DEFINITIONS While viewing the Emergency Setting menu Press HELP select SET and press ENTER Diff above target for emergency Set a value above temperature target at which the emergency card enters emergency operation Diff below target for ...

Page 56: ... according to the mode installed Farm Premium enables controlling the water cycle times using relays and controlling the water pressure using analog input and output sensors The two methods are complimentary A user can use either one alone or both Relay Control Sensor Control NOTE The two methods are complimentary 4 12 1RELAY CONTROL You can specify up to 50 time periods 1 In Installation Relay La...

Page 57: ... day and time o WOD Relay Enable the required relays o Pressure Specifies the required water pressure The unit that appears is the unit defined in Installation Setup pressure unit page 106 4 In Device Water on Demand Help set the parameters optional 5 In Service WOD Calibration a Enter the first pressure and voltage data points b Repeat for second data point c Set the Help definitions optional ref...

Page 58: ... option to remain in natural ventilation refer to Minimum Wind Speed for Tunnel Temp The wind speed must be within the wind speed band The wind direction must be within the user defined area NOTE Including the wind speed and direction in Natural Ventilation calculations is optional and requires in the installation and configuration of additional equipment If the weather conditions meet the above r...

Page 59: ...urtain s direction When making Natural Program calculations the controller only takes into consideration winds coming from a certain direction Any wind whose source is outside of this area is disregarded The number entered here defines the area the number entered 90 Figure 10 If you enter 90 the range is from 0 180 If you enter 45 the range is from 315 135 Figure 8 Wind Direction Sensor Definition...

Page 60: ...NG NATURAL OPERATION Natural Operation defines how the controller functions in Natural Ventilation Low Temperature Difference The band below the Current Target Temperature in which Natural Programming operates inside temperature High Temperature Difference The band above the Current Target Temperature in which Natural Programming operates inside temperature Step size Sets each levels step incremen...

Page 61: ...urtain maximum opening percentage to this point o Between these levels the controller opens the curtain based on a curve o Wind Rain Low speed o Wind Rain High speed 4 13 6NATURAL PROGRAM HOT SCREEN When the Main Screen is displayed press 5 to view the Natural Program Hot Screen The Hot Screen display depends on the Natural Program Status 4 13 6 1 Ventilation is Not in Natural Mode When Farm Premi...

Page 62: ...matically calculate most suitable Power Ventilation Level depending on the Target Temperature and current Inside Temperature Natural Tunnel The controllers automatically calculates the most suitable ventilation level depending on the Target Temperature and current Inside Temperature minimum or tunnel 4 14 Feed Scale Program NOTE Broiler Mode supports this function Feed Scale enables mixing differe...

Page 63: ...nt of feed required for the current growth day In the example shown above the growth day is Day 2 Farm Premium calculates the curve from Day 1 to Day 5 and adjusts the numbers accordingly 4 14 1FEED SCALE HELP SET DEFINITIONS Define o Time What time the hopper begins distributing feed to the birds or animals o Maximum Portion Weight Enter the feed scale container size o Maximum Auger Time minutes ...

Page 64: ...zation is indicated There are three settings Default Slower Faster NOTE Munters recommends leaving this parameter at the default level o Valve Close Time seconds Set the delay in time if any that the valve emptying the feed scale closes o Feed Tare A D count This specification is used for certain tests performed by a certified technician NOTE Munters recommends leaving this parameter unedited 4 14...

Page 65: ... if the feed has reached the maximum level in the feed bin Define this sensor in Install Digital Sensor This screen shows the sensor s current status If the feed reaches this sensor an alarm is generated Alarm This parameter shows if there are active alarms View the alarms on the Main Screen ...

Page 66: ...LARM RESET 7 FAIL SAFE SETTING 8 PASSWORD 9 RELAY CURRENT MANAGEMENT 1 ANIMAL INVENTORY 2 FEED INVENTORY 3 TIME DATE 4 GROWTH DAY GROUP 5 ALARM SETTING 6 ALARM RESET 7 FAIL SAFE SETTING 8 PASSWORD 9 RELAY CURRENT BIRD INVENTORY Male Female Total Add Dead Birds Add Culled Birds Moved Birds Placed 0 0 0 10000 0 0 0 5000 0 0 0 15000 Today s Dead Birds Today s Culled Total Dead Birds Total Culled Tota...

Page 67: ... of the month and press ENTER 2 Select the month and press ENTER 3 Type the two digit year and press ENTER 4 Enter the feed quantity under the silo and press ENTER The cumulative total appears in the Total Feed row 6 To delete an entry change the quantity to zero for all silos and press ENTER Exit the menu and the entry disappears when you enter the menu again 7 Set the Feed Alarms page 71 If you ...

Page 68: ...Day and Flock Number Current Growth Day Enter current growth day if necessary It is possible to enter negative growth days up to 2 If you reset the growth day for a new flock using this tool your old history data does not clear Use New Flock function to clear out old history in preparation for new birds Group Flock No The controller automatically increments the flock number each time you choose Ne...

Page 69: ... Sensor readings above this reading are rejected This generates a sensor out of range alarm This does not apply to the special Circuit Breaker Sensor or Outside Temperature Sensor Sensor Alarm Differential from Low Alarm Individual sensor or zone alarm if any active sensor reads this much or more below the Control Temperature Curve Low Alarm Temperature page 15 Sensor Alarm Differential from High ...

Page 70: ...e Choose whether to shut the feed systems off after a feeder overtime alarm Options No All augers and feeders remain on All Al augers and feeders shut down Related Only the specific auger from which the alarm originated and it feeders shut down NOTE This alarm functions in the Broiler mode only NOTE Setting the Feeder Off During Overtime to All in either the Auger Overtime Alarm or the Feeder Over...

Page 71: ...to start increasing the overflow limit automatically Days prior to the First Day use the First Day overflow limit days following the first day have an incremental curve toward the LAST DAY OVERFLOW parameter setting Overflow on First Day Number of gallons liters per minute that generate an overflow alarm on the first day Last Day Set the last day for the overflow curve Overflow on Last Day Set the...

Page 72: ...ent The alarm ceases when the CO2 drops below this level If the user acknowledges the alarm the alarm messages temporarily cease for the reminder time Humidity Sensor Alarm Humidity High Level Alarm Set the maximum allowed humidity level above which an alarm is sent The alarm ceases when the humidity drops below this level If the user acknowledges the alarm the alarm messages temporarily cease for...

Page 73: ...s as set in Control Static Pressure If you select SIREN ONLY the alarm relay returns to the no alarm condition but the emergency pressure status continues Restores normal operation after a feed overrun situation that calls for turning off the feeding system If the feed monitor senses the cross auger runs too long it trips a feed overrun alarm and optionally turns off the feed system If you select ...

Page 74: ...he controller with a password an event is recorded in the History Table of Events NOTE If your controller uses passwords the controller also requires a password entry to acknowledge switch position changes If the switch change is not acknowledged the controller signals an alarm 5 9 Relay Current NOTE The Relay Current feature supports single phase electricity only This menu configures the relay cu...

Page 75: ...alue However the augers minimum can go down to 0 0 amperes 5 10 Farm Thermo 5 Temperature Curve Munters Farm Thermo 5 is a five stage digital thermostat that works in conjunction with Farm Premium Controllers or as a stand alone unit When wired to the Farm Premium you can use the Farm Premium to set the Farm Thermo 5 s stage activation temperatures which is easier than setting the temperatures on ...

Page 76: ... is sent out After configuring the Farm Thermo 5 disconnect the unit from the Farm Premium and reconnect the Extension box If the Extension box is not reconnected Farm Premium sends out alarms 5 10 1FARM THERMO 5 TEMPERATURE CURVE SET DEFINITIONS While viewing the Farm Thermo 5 Temperature Curve menu Press HELP select SET and press ENTER Define the parameters as required o Stage 1 5 Diff Enter the...

Page 77: ...u 6 1 Scale Layout Use Scale Layout to define the scales or silos connected to the controller Figure 17 Pig Mode Scale Layout Figure 18 Broiler Layer Mode Scale Layout Define the weighing device attached to each channel of the scale option card SCALE 1 SCALE LAYOUT 2 FEED BIN SETTING 3 TEST 4 CALIBRATION SCALE 1 SCALE LAYOUT 2 GENERAL SETTINGS 3 BIRD SCALE SETTING 4 SILO SETTING 5 BIRD CURVE 6 HIS...

Page 78: ...weights within this percentage of the average as uniform Default is 10 Curve Selector for mixed There are three standard pairs of pre programmed weight curves If you use the mixed weighing method edit the curves to match your expected growth profile BROILER TURKEY or BREEDER Weigh During Feed Days Allow weight data to be recorded on feed days When set to NO this data is discarded Default No 6 2 1 ...

Page 79: ...os must be defined in Scale Layout for the following parameters to be functional Minimum Emptying Weight Default 20 Kg Define the accumulated emptying weight from the bin during feeding time for it to be recorded as an event Once it has been recorded the counter resets Minimum Filling Weight Default 2000 Kg Define weight required to be filled during loading to be recorded in History Feed History H...

Page 80: ... General Settings NOTE Only Broilers Layers Mode support this function Edit the growth days and weights for the bird curves to fit individual preference 6 5 1 BIRD CURVE HELP SET DEFINITIONS While viewing the Bird Curve menu Press HELP select SET and press ENTER Bird Curve Offset Enter the factor used to adjust the weight curve This amount is added to the Now field Range 0 0 10 0 Kg Lb 6 6 History...

Page 81: ...ustry standard 10 uniformity number of birds per 100 within 10 of the average weight and the Coefficient of Variation or C V is the normalized standard deviation standard deviation divided by average times 100 6 7 Feed Conversion This screen displays the amount of feed converted into the bird s weight NOTE Only Broiler Layers Mode supports this function HISTORY Day Avg NO S D Unif C V 17 18 19 20 ...

Page 82: ...alibrates the scales and silos connected to the controller 1 In Scale Scale Layout refer to page 77 select the required scale types 2 In Scale Calibration calibrate the scales CAUTION Do not use scales while calibrating 6 9 1 SCALE CALIBRATION 1 Follow instructions on the bottom section of the screen 2 Wait until the progress bar displayed shows 100 3 Place a known weight on the scale and enter it...

Page 83: ...TION PROCESS CHANNEL 1 Place a Known Weight and enter the Weight 1 000 CALIBRATION PROCESS CHANNEL 1 GOOD CALIBRATION 3 5 CALIBRATION PROCESS CHANNEL 1 4 100 CALIBRATION PROCESS CHANNEL 1 25 2 SCALE CALIBRATION Channel Scale Weight Factor Offset Silo 1 Silo 2 Silo 3 None 0 1008 1008 0 0 2000 2000 2000 2000 CHANNEL 1 Press ENTER to Calibrate or RIGHT ARROW to change Factor or Offset 1 CALIBRATION P...

Page 84: ...ic silo Map up to four augers to four silos one each NOTE Only Broilers Layers mode supports this function NOTE Define the silo channel in Scale Layout page 77 NOTE Define the feeding schedule in Water Feed page 51 SILO AUGER LAYOUT Silo Auger 1 2 3 4 Auger 1 Auger 2 None None ...

Page 85: ...closer to the maximum than the minimum NOTE If two humidity sensors are installed this screen displays their average The History View display shows reading of both sensors only if they have been selected for logging 7 3 CO2 The CO2 history menu stores minimum average and maximum inside CO2 levels by growth day The average is weighed therefore if most of the day has been high CO2 levels the average...

Page 86: ... are installed and calibrated refer to Current Sense Relay Calibration page 103 feed consumption data of each auger is based on the current sense calculation method settings and actual auger run time The run time is calculated based on the measured current when the actual current is higher than the nominal value refer to Relay Current page 74 Feed Count If a feed count sensor is installed feed con...

Page 87: ...h Date Flock New Flock New events push out the older events Typical events recorded are switch changes entry into tunnel mode natural or minimum ventilation alarm resets ventilation mode changes and more The Table of Events is an excellent tool to determine whether your controller is going in and out of tunnel due to marginal settings as well as finding and identifying problems NOTE Go to the Tabl...

Page 88: ...ion This menu displays the daily power consumption in kWh of the heaters fans lights and other equipment and the change from the previous day NOTE Current sense relays are required for this function to be enabled single phase electricity only 7 13 Ammonia History This screen displays the minimum average and maximum ammonia levels by growth day ...

Page 89: ...Status page 93 8 1 Switches Relays This menu displays a screen of identified switches and relays installed in the controller Use this option to determine faulty hardware The Farm Premium supports a maximum of 20 relays Farm Premium P 30 relays Farm Premium P XL 40 relays Farm Premium Farm Premium XL 50 relays Farm Premium XL 50 Up to 40 extra relays using a Farm Premium Extension The following scr...

Page 90: ... sensors with this menu Define sensors in Installation Analogue Sensors SWITCHES RELAYS 01 02 03 04 05 06 07 08 09 10 Aut Aut Aut Aut Aut Aut Aut Aut Aut Aut 11 12 13 14 15 16 17 18 19 20 Off Off Aut Aut Aut Aut Aut Aut Aut Aut 21 22 23 24 25 26 27 28 29 30 Aut Aut Aut Aut Aut Aut Aut Aut Aut Aut 31 32 33 34 35 36 37 38 39 40 On Aut On Aut Aut Aut Aut Aut Aut Aut 41 42 43 44 45 46 47 48 49 50 Aut ...

Page 91: ...uch as the Arad Water Meter or micro switches You can apply a short open input to each channel the response is then displayed NOTE The water meter quantities appear on the main screen or on Hot Screen 0 8 5 Analog Output This screen tests light dimmers variable speed fans and variable heaters 1 Scroll to the required output 2 Enter the test voltage and verify that the device is operating Define se...

Page 92: ...ication networks A multiplexer in loop back mode is used to test the communication The Farm Premium follows its own communication to check for failed hardware Follow the instructions displayed on the screen ANAGLO OUT TEST Output Sensor 0 10v 1 Light Dimmer 1 0 0 2 Light Dimmer 2 0 0 3 Light Dimmer 3 0 0 4 Var Heat 0 0 5 W O D 0 0 6 None 0 0 7 None 0 0 8 None 0 0 STATIC PRESSURE A D Counts 126 To ...

Page 93: ...n 8 9 Emergency Status This screen displays the emergency cards status if installed Emergency card sensor temperature Current set or target temperature Backup battery level Minimum ventilation cycle timer ON OFF time HARDWARE CHECKLISTE Description Found Relays Analog Input Digital Input Analog Output Scales Static Pressure Alarm N C Emergency Card N O Switch Card N C Switch Card Vent Board Curtai...

Page 94: ...re sensors are typically accurate to approximately 0 5º F within the range of temperatures for poultry production Calibrate them in this menu by adding subtracting a constant correction factor to each sensor Adjust the sensor of your choice with the left right arrow keys SERVICE 1 TEMP CALIBRATION 2 HUMIDITY CALIBRATION 3 CO2 CALIBRATION 4 STATIC PRESSURE CAL 5 LIGHT SENSOR CALIBRATION 6 FEED CALI...

Page 95: ...ler should double check that you are calibrating the correct sensor You might warm cool the sensor temporarily to see which sensor changes temperature appropriately 5 Once you determine the correct temperature and allow approximately one minute for stabilization in the water adjust the sensor reading at the controller 6 Offset the factor using the left right arrow keys Refer to Temperature Curve p...

Page 96: ...means that there is zero 0 static pressure CAUTION The Static Pressure sensor is factory calibrated Only calibrate the sensor if you have reason to believe that they are producing inaccurate results NOTE Run Farm Premium for a few hours so that the temperature in the box becomes stable and only then calibrate CAUTION DO NOT blow the air into the hose to see of the pressure changes The sensor is se...

Page 97: ...ight sensor 1 Go to Install Analog Sensors page 109 2 Define one sensor as a light sensor 3 Go to Device Light page 49 4 Press Help highlight Set and press Enter 5 Scroll down to Light Sensor Active and set to Yes 6 Place the sensor in the required location 7 Go to Service Light Sensor Calibration 8 When the outside light is bright enough press Enter STATIC PRESSURE CALIBRATION A D Counts 110 Disc...

Page 98: ...on Farm Premium supports up to four dry contact pulse output water meters Enter the quantity of water per pulse for your water meters 9 8 Ventilation Potentiometer Calibration Use this screen to calibrate the ventilation potentiometer control Potentiometer calibration is required before ventilation can be controlled via a potentiometer Before calibrating the potentiometers o Disable the static pre...

Page 99: ...usual water line 112 Water Bypass The control s supplementary to bypass the water pressure regulator 113 Water line 1 through 122 Water line 10 Individual water line supplementary to select the line to flush During normal operation only relay 111 water main is active During flushing relay code 112 is active together with each of the individual water line relays in turn Configure up to 20 flush tim...

Page 100: ...t at Time Set the desired time to adjustment Feeder Window Stop Feed Before Adjust min Set the amount of time to stop feeding before adjustment begins Time from Close to Open sec Set the amount of time after stopping the feeding before opening the feeder s window Feed Line Movement Time per 10 inch sec Set a number of seconds needed to move the feed line 10 inches FEEDERS AND DRINKERS Day Window P...

Page 101: ...er for quick programming 1 Insert data plug as shown 2 Save controller settings 9 11 2SAVING TO AN SD CARD This menu enables the user to save the program settings to an SD card and transport them to another controller NOTE If both a data plug and SD card are inserted the data plug takes priority and that option appears on the screen Verify that the SD card is in place The SD card must have at leas...

Page 102: ...ta plug takes priority and that option appears on the screen Verify that the SD card is in place The SD card must have at least 20K of free space To load settings 1 Go to Service Load Settings 2 In the screen that appears select YES and press Enter 3 Select the required settings and press Enter 4 Wait for the settings to upload ACTION WILL OVERWRITE EXISTING CONTROLLER DATA ARE YOU SURE YES NO REA...

Page 103: ...ROM SD CARD 1 Setting 1 8 Jan 13 12 00 2 Setting 1 15 Jan 13 12 00 3 Setting 1 23 Mar 13 12 00 4 Setting 1 15 Jun 13 12 00 5 Setting 1 15 Nov 13 12 00 6 Setting 1 01 Jan 14 12 00 RELAY CURRENT CALIBRATION Relay Function Measure Current ON 31 Heat 6 Start 0 0 32 Heat 7 Start 0 0 33 Heat 8 Start 0 0 34 Exh Fan 5 Start 0 0 35 Exh Fan 6 Start 0 0 Warning The selected equipment will be turned ON now fo...

Page 104: ... This parameter reduces the water pressure a user defined factor 1 In Install Setup define the Pressure unit 2 In Service WOD Calibration Help define the reduction factor Water pressure is reduced by 1 50 bar or PSI The factor is accurate to two decimal points 9 16 Ammonia Calibration Define an analog sensor as ammonia sensor WIND DIRECTION CALIBRATION Direction Calibration Wind Direction 6 14 50 ...

Page 105: ...reason to believe that they are producing inaccurate results Define the following o Ppm at 0 VDC Parts per million at 0 VDC o Ppm at 5 VDC Parts per million at 5 VDC o Factor ppm ppm shift from the current reading o Ammonia ppm Current ammonia reading o Adjust the Farm Premium reading as needed using the left right arrow keys o Refer to Ammonia Treatment AMMONIA CALIBRATION PPM at 0VDC 0 PPM at 5V...

Page 106: ...ar Inches of WC Water Column Pascal cm of WC mm of WC None Wind Speed Unit Km Per Hour Mile per Hour Meter per Sec Feet per Sec Fan Air Capacity Unit Cubic feet per minute CFM Cubic meter per hour M3 H Length Unit Meter Feet Weight Unit Pounds LB Kilograms KG INSTALLATION 1 SETUP 2 RELAY LAYOUT 3 ANALOG SENSORS 4 DIGITAL SENSORS 5 ANALOG OUTPUT 6 VENT CURTAIN SETUP 7 CURTAIN SETUP 8 TEMP DEFINITIO...

Page 107: ...er manually 2 If the required code is 100 and above use the keys before selecting and then press a two digit number For example 135 would be 35 3 To duplicate relays use the As Relay X where X stands for a relay number defined already in the system Enter relays according to equipment installation I O list of technician using up down arrow keys If you have installed Current Sense relays Farm Premiu...

Page 108: ...15 8 Cooling 4 9 Cooling Pad 4 10 Fogger 4 11 Vent Open 4 12 Vent Close 4 13 Tunnel Open 4 14 Tunnel Close 4 15 Curtain Open 4 16 Curtain Close 4 17 Attic Open 1 18 Attic Close 1 19 Vent Speed 1 20 Light 4 21 Water 4 22 Feeder 4 23 Auger 4 24 Extra System 4 25 Alarm N C 1 26 Fail Safe N C 1 27 Feeder Win Open 1 28 Feeder Win Close 1 29 Feeder Line Up 1 30 Feeder Line Down 1 31 Drink Line Up 1 32 D...

Page 109: ...breaker as analog sensors These sensors measure a continuous range rather than just on or off Enter temperature humidity sensors wired to each input setup according to technician NOTE If sensor numbers duplicate the sensors average ANALOG SENSORS In Function Num 1 None 0 2 None None 0 3 None 1 Temp Sensor 0 4 None 2 Hum Sensor In 0 5 None 3 Hum Sensor Out 0 6 None 4 CO2 Sensor 0 7 None 5 Light Sen...

Page 110: ... Floor heat up to two Pig Mode only Install analog output cards Enter sensors wired to each input setup according to technician The above is an example of an analog output configuration DIGITAL SENSORS In Function 1 None None 2 None 1 Water Meter 3 None 2 Cool Pad Water Meter 4 None 3 Fogger Water Meter 5 None 4 Feed Count 6 None 7 None 8 None DIGITAL SENSORS In Function Num 1 Water Meter 1 2 Auge...

Page 111: ...number 3 Enter the minimum and maximum voltage outputs according the actuators requirements However to enable opening and closing manually a relay must be mapped to the analog output NOTE The following steps are optional 4 Go to Installation Relay Output 5 Define a relay as AS Analog Out 38 6 Place the cursor in the number column and enter the recorded output number 7 Repeat for each relay NOTE If...

Page 112: ...ired Analog Sensors page 109 2 Map the curtain vent tunnel inlet to a potentiometer in this screen NOTE The number of the devices that you can map equals the number of potentiometer relays NOTE The symbol designates an analog output device 3 Calibrate the potentiometer Ventilation Potentiometer Calibration page 98 NOTE After calibrating the potentiometer the times shown here change to reflect the ...

Page 113: ... number of steps for automatic calibration Set calibration point for curtain after desired amount of curtain opening closing steps During calibration if the curtain is open more than 50 it opens to 100 calibrates and returns to the previous position If the curtain is open less than 50 it closes to 0 calibrates and returns to the previous position Default 99 Power Vents Calibration This parameter e...

Page 114: ...sensors cause the current average to apply to devices when no specific sensor is assigned to them The current average substitutes for either failed or missing sensors NOTE Sensors 10 18 require installing a second analog card Press key to add remove to assign temperature sensors to corresponding function Refer to Temperature Curve page 15 Assign Temperature Sensors as required in Install Temp Defi...

Page 115: ...e NOTE The symbol designates an analog output device 10 9 House Dimensions The screen allows the user to set its house dimensions Set it according to actual house size These dimensions are used for calculating the wind chill factor the chilling effect of the wind that can significantly lower the temperature Define height width and length of house controller calculates total area To set the dimensi...

Page 116: ...e connected to a Farm Premium Controller via a o communication card or o analog output card In the event that o there is no analog output card installed or o there is a an analog output card but all outputs are defined for other devices this screen maps the Farm Light Dimmers connected via a communication card NOTE If the Farm Premium Controller has an analog output card you can map multiple RLD u...

Page 117: ...ctive Output Definition Alarm Can be either active or not Note that this always appears last Heat Indicates operating heat number Heat Hi Indicates operating heat high number Tun Fan Indicates operating tunnel fan number Exh Fan Indicates operating exhaust fan number Stir Indicates operating stir fan number Cool P Indicates operating cool pad number Fogger Indicates operating fogger number Inlet T...

Page 118: ...cated in low curve temperature or when the Control Mode HELP SET Temperature Curve parameter is set to OFF Hum Treat Indicates when treatment occurs Cool flush Indicates when flush occurs Nip Flush Indicates when flush occurs Table 4 Table of Events Event Event Explanation Power Off Appears when power is off Power On Appears when power is on Cold Start Appears when cold start is done Change level ...

Page 119: ...rs when minimum low pressure alarm is enabled Tun L P Alarm Dis Appears when tunnel low pressure alarm is disabled Tun L P Alarm Ena Appears when tunnel low pressure alarm is enabled Visitor Log in Appears when the visitor logs in with his password User 1 5 log in Appears when the user logs in with his password Owner log in Appears when the owner logs in with his password Change Visitor pass Appea...

Page 120: ...2 Layers Mode Active Sensors SENSORS AV TEMP ACTIVE Temp1 37 9 27 5 Heat 1 Temp2 16 2 Heat Hi 1 Temp3 28 2 STATUS Tun Fan E Tmp1 28 8 08 53 06 Exh Fan E Tmp2 28 4 Day 5 Stir Press 23 Set 25 0 Cool P Out T 23 9 Level 3 Fogger Hum In 58 7 Min Vent Inlet 1 55 Hum Out 61 9 FanOff 176 Inlet 2 55 Weight 0 000 Inlet 3 50 Weights 0 Tun 1 0 4 MESSAGES Alarm 0 2 Low Feed At Silo 2 ACTIVE Heat 1 Heat Hi 1 Tu...

Page 121: ...Help Set this becomes the minimum position for the tunnel inlet NOTE Refer to Vent Curtain Levels Help Set Definitions for Help Set details 12 2 1LAYER INLET CONTROL Inlets can be controlled via two methods Pressure In this mode inlets open and close according to the static pressure Position In this mode inlets open and close according to the temperature To select the inlet control method 1 Go to ...

Page 122: ...2 2 1 2 Position Control When set to Position control the inlets open and close according to the temperature As the actual temperature differs from the target temperature the inlet opens or closes The number shown is the opening percentage Level Read only Inlet Average Set the opening position for all inlets by level Inlet 1 2 3 12 Set the opening level for an individual inlet by level Set up to 1...

Page 123: ...is 2 above the target temperature the inlet opens an additional 6 Default 1 F Delay for Compensation minutes As the temperature sensors record changes in temperature Farm Premium waits this amount of time before changing the inlet position Default 5 minutes Maximum Compensation Opening Inlet opening does not differentiate from the set level more than this amount regardless of the temperature Defau...

Page 124: ...ach degree The target temperature is 80 0 with a hysteresis of 0 5 Between 79 5 to 80 5 the inlet remains at 50 If the temperature rises to 81 0 the opening goes to 53 12 3 Layer Dimmers Layer mode supports up to ten analog dimmer channels ANALOG OUTPUT Out Num Function Num Min V Out Max V Out 1 Light Dimmer 1 0 0 10 0 2 Light Dimmer 2 0 0 10 0 3 Light Dimmer 3 0 0 10 0 4 Light Dimmer 4 1 0 9 0 5 ...

Page 125: ...t functions as Temperature Sensors and as an Egg Room Humidity sensor NOTE Refer to Analog Sensors page 109 for details on this screen 3 In Install Temperature Definition configure which temperature sensors operate in the egg room NOTE Refer to Temperature Definition page 114 for details on this screen 4 In Service Humidity Calibration calibrate the Egg Room humidity sensor RELAY LAYOUT Relay Func...

Page 126: ...ifier relative humidity percentage 6 In Control Egg Room Help Set configure the following alarm parameters o Low Temperature o High Temperature o Low Humidity o High Humidity o Delay minutes HUMIDITY CALIBRATION Sensor Humidity Factor In 1 58 9 2 3 In 2 58 9 2 3 Out N A Egg Room 67 2 0 Press Left Right Arrows to Calibrate SENSORS Temp1 37 9 Temp2 16 2 Temp3 28 2 E Tmp1 28 8 E Tmp2 28 4 Egg Room 28...

Page 127: ... auger o Set the water feeder and auger lines to Continuous Cycle or Off 3 Go to Device Water Feed Help optional 4 If a device is set to Cycle define the Water Feeder Auger On and Off times EGG ROOM ALARM Low Temp 62 6 High Temp 71 6 Low Humidity 70 High Humidity 80 Delay minute 60 WATER FEED Time Water Feeder Auger From To 1 2 1 2 1 2 4 00 4 45 5 00 7 00 0 00 0 00 0 00 0 00 0 00 0 00 4 30 5 15 5 ...

Page 128: ...l Relays To and From times can overlap For example in the table above one line goes from 4 45 to 5 15 and the next line goes from 5 00 to 5 30 If there is overlap and contradictory configurations the priority is Continuous Cycle Off In the example above Water Line 2 will run in a cycle from 5 00 until 5 30 Feeder Line 1 will be on 4 45 until 5 15 even though the line 3 turns off the feeder 13 3 Eg...

Page 129: ...ing and closing up to four Nest lines at specific times Birds can then leave their Nests and return 1 In Installation Relay Layout designate up to four relays each as Nest Open and Nest Close valves 2 In Device Nest define the parameters o Open Time The time each Nest lines doors open o Duration The amount of time required for the Nests to open o Close Time The time each Nest lines doors close o D...

Page 130: ...istribution When this disconnect happens a signal is sent from the arm to the silo informing the latter that it must be refilled Farm Premium enables recording these signals in the Events History To define the Scale Arm 1 Go to Install Digital Sensors 2 Define one sensor as Scale Arm In History Table of Events Feed Delivered appears when the mechanical arm disconnects WORK ROOM CONTROL Function On...

Page 131: ... Munters AB 2015 131 TABLE OF EVENTS Event Day Time 1 Feed Delivered 1 13 27 05 ...

Page 132: ...ade in writing within eight days of the discovery of the defect and within 12 months of the delivery of the defective product Munters has thirty days from the date of receipt in which to take action and has the right to examine the product at the customer s premises or at its own plant carriage cost to be borne by the customer Munters at its sole discretion has the option of replacing or repairing...

Page 133: ...nt on the basis of the information supplied with regard to installation tools and consumables required for fitting and installation lubricants necessary for commissioning and maintenance It is mandatory to purchase and use only original spare parts or those recommended by the manufacturer Dismantling and assembly must be performed by qualified technicians and according to the manufacturer s instru...

Page 134: ...3 52 11 Japan Munters K K Phone 81 3 5970 0021 Korea Munters Korea Co Ltd Phone 82 2 761 8701 Mexico Munters Mexico Phone 52 818 262 54 00 Singapore Munters Pte Ltd Phone 65 744 6828 South Africa and Sub Sahara Countries Munters Pty Ltd Phone 27 11 997 2000 Spain Munters Spain S A Phone 34 91 640 09 02 Sweden Munters AB Phone 46 8 626 63 00 Thailand Munters Co Ltd Phone 66 2 642 2670 Turkey Munter...

Reviews: