103
9.13
Current Sense Relay Calibration
NOTE:
The Current Sense relays supports
single phase electricity
only.
This menu calibrates the amount of current that passes through Current Sense relays. Calibration enables
configuring the minimum and maximum permissible currents.
To calibrate the current sense relay:
1. Define the relay (refer to page 107).
2. Select
Service > Relay Current Cal
. The following screen appears.
3. Select a relay and click Enter.
NOTE:
Set the relay to Auto.
4. Repeat for each current sense relay.
5. To set the minimum and maximum voltages, alarms and 110/220 voltage, refer to Relay
Current, page 74.
READ FROM SD CARD
1. Setting #1
8-Jan-13
12:00
2. Setting #1
15-Jan-13
12:00
3. Setting #1
23-Mar-13
12:00
4. Setting #1
15-Jun-13
12:00
5. Setting #1
15-Nov-13
12:00
6. Setting #1
01-Jan-14
12:00
RELAY CURRENT CALIBRATION
Relay Function Measure
Current
ON
31
Heat 6
Start
0.0
32
Heat 7
Start
0.0
33
Heat 8
Start
0.0
34
Exh. Fan 5 Start
0.0
35
Exh. Fan 6 Start
0.0
Warning!!!
The selected equipment will be turned ON
now for current reading adjustment WAIT
till operation completion for 15 sec
Verify that the relay switch is AUTO
RELAY CURRENT CALIBRATION
Relay Function
Measure
Current
ON
31
Heat 6
Done
0.2
32
Heat 7
Done
0.2
33
Heat 8
Done
0.2
34
Exh. Fan 5
Done
3.8
35
Exh. Fan 6
Done
4.3
Warning!!!
The selected equipment will be turned ON
now for current reading adjustment WAIT
till operation completion for 15 sec
Verify that the relay switch is AUTO