Proximity to Edge %: Curtain will open or close based on this proximity to the edge. For
example, when set to 10%, the curtain closes when the opening is less than 10% and opens
completely when the opening is greater than 90%.
•
Close Below This Temp. (out): Curtains close when the outside temperature reaches this point.
This parameter requires defining a temperature sensor as an outside sensor (refer to
Temperature Definition).
NOTE:
The Proximity to Edge % parameter takes priority over the Close Below This Temp parameter.
Meaning, if the outside temperature mandates closing the curtain, the curtains will still open if
they are within the proximity defined in the Proximity to Edge parameter.
10.7
Temperature Definition
This screen assigns specific temperature sensors for various brood setups and for heater zones. Moreover,
assigning sensors to particular devices is possible. Note that if the sensors selection remains blank, the
default value is assigned.
Choose 1 to 18 temperature sensors for each item listed by using the '+/-' keys. The house, brooding and
tunnel sensors cause the current average to apply to devices when no specific sensor is assigned to them.
The current average substitutes for either failed or missing sensors
.
NOTE:
Sensors 10 – 18 require installing a second analog card.
•
Press +/- key to add/remove
to assign temperature sensors to corresponding function.
•
Refer to Temperature Curve, page 15.
•
Assign Temperature Sensors as required in
Install > Temp Definition
. Devices that do not
accept temperature sensors, such as Exhaust Fans, Tunnel Fans, Feed and Light do not appear.
NOTE:
If you are using two (2) input analog cards, the screen displays Temp. Sensor(s) 1-18 (refer to
above screen capture).
NOTE:
When an attic sensor is not installed, the attic vent is disabled.
NOTE:
The
~
symbol designates an analog output device.
Note that Exhaust Fans and Tunnel Fans do not appear because the Ventilation Levels defined in
Device >
Levels of Ventilation
control their operation. Stir Fans appear even though the
Device >Stir Fan Levels
apply to them because they simultaneously operate according
Device > Stir Fan Programs
where specific
sensor assignments are required in Program B and recommended in Program C.
TEMPERATURE DEFINITION
Function
Temp. Sensor
1 2 3 4 5 6 7 8 9
Full House
√√√▪ ▪ ▪ ▪ ▪
Tunnel
setting
▪ ▪ ▪ ▪ ▪ ▪ ▪
Attic
▪ ▪ ▪ √ ▪ ▪ ▪
Outside
▪ ▪ ▪ ▪ √ ▪ ▪
Stir Fan 1
▪ ▪ ▪ ▪ √ ▪ ▪
~ Stir Fan 2
▪ ▪ ▪ ▪ √ ▪ ▪
~ Var. Heat 1
▪ ▪ ▪ ▪ √ ▪ ▪