35
select
01
sender
MultiGen GENERATOR MONITORING SYSTEM
MultiGen GENERATOR MONITORING SYSTEM
psi
ACTION :
Press
COMMENTS :
If third line of text equals
00 the unit is already in
custom mode, if not proceed
to next action
ACTION :
Press
COMMENTS :
Press until the number
on the third line equals 00
MultiGen GENERATOR MONITORING SYSTEM
MultiGen GENERATOR MONITORING SYSTEM
psi
select
sender
00
The following sequence of events shows programming of 5
pressure points and 5 corresponding resistance values as
shown in table on page 34. The first point that is
programmed must always be the point that corresponds to
the lowest pressure value. In this example it is 0 psi, and
0 psi = 220 ohms. So the first pressure point that is
programmed in is 0 psi. The first resistance point that is
programmed in is 220 ohms see page 40
GENMOM.PM5
20/03/100, 10:31
35