4.2 Programming of nominal voltage and current inputs
and ratios.
The SUPPLY programming mode allows the user to
program the nominal voltage and current inputs and ratios.
Please note the ratios can be changed as long as the
secondary (the input to the MultiGen) stays as shown on
the data label which is on the side of the product. For
example if the MultiGen had been set by the factory to have
a C.T. ratio 200/5A and the change required was for input
C.T. ratio to be 500/5A this can achieved by program
changes. But if the change required was for a C.T. ratio
500/1A then the unit would have to be returned to the
factory or distributor to have the internal C.T. changed
14