80
3X REGS
Registers
Modbus
Reg, Start
MultiGen
name
Addr, (dec)
Addr. (hex) Type
Volts L2-L1
30001
0000 GM/SM 4/9
Volts L3-L2
30002
0002 GM/SM 4/9
Volts L1-L3
30003
0004 GM/SM 4/9
System Volts L1*
30004
0006
All types
System Volts L2*
30005
0008 GM/SM 4/9
System Volts L3*
30006
000A GM/SM 4/9
System Amps L1
30007
000C
All types
System Amps L2
30008
000E GM/SM 4/9
System Amps L3
30009
0010 GM/SM 4/9
System Hz
30010
0012
All types
Oil Pressure
30011
0014
GM1,4,9
Temperature
30012
0016
GM1,4,9
DC Volts
30013
0018
GM1,4,9
Hours Run
#
30014
001A
GM1,4,9
System W
30015
001C
All types
System VA
30016
001E
All types
* In 3 wire mode system V1, V2, V3 will have the same
value as volts L2-L1, L3-L2, L1-L3.
# In the Hours Run register all data is stored in minutes.
Response from slave format:
Node Addr][04][Byte count][Data (byte count bytes)][CRC(2
bytes)]
The table below lists the parameter with the Modbus
equivalent address and its address within the
MultiGen. Any data requested that isn't applicable to the
conditions column will return the value -ve infinity
(FFFFFFFFh)