The following sequence of events shows programming of 5
temperature points that correspond to the 5 resistance
values as shown in table on page 45. The first point that is
programmed must always be the point that corresponds to
the lowest temperature value. In this example it is 100 °F
and 100 °F = 950 ohms. So first temperature point that is
programmed in is 100 °F. The first resistance point that is
programmed in is 950 ohms see page 45.
pnt 1
0000
°F
ACTION :
Press
COMMENTS :
The Multigen is now in
custom sender mode, and
point 1 (pnt 1) has to be
programmed.Point 1 = 100
°F (0100). The cursor
flashes under the 2nd digit.
MultiGen GENERATOR MONITORING SYSTEM
MultiGen GENERATOR MONITORING SYSTEM
°F
pnt 1
0100
47
MultiGen GENERATOR MONITORING SYSTEM
MultiGen GENERATOR MONITORING SYSTEM
ACTION :
Press
COMMENTS :
Pressing scrolls the digit
with cursor flashing below it
from 0 to 9. When the digit
required is displayed Press
to store. In this example the
1st point is 100 °F . Press
when 1 is displayed.