5.2 Putting into operation after scheduled out-of-service-period
Preconditions
☑
Engine is stopped and starting disabled.
Putting into operation
Item
Action
Lube oil system
Check engine oil level (→ Page 237);
Coolant circuit
Check engine coolant level (→ Page 244).
Check charge-air coolant level (→ Page 265).
Coolant circuit
Heat engine coolant with coolant preheater.
Fuel prefilter
Drain water (→ Page 215), (→ Page 217).
Monitoring system
Carry out lamp test (see manufacturer's documentation).
Engine/generator control
system
Switch ON;
Select operating mode, e.g.: MANUAL, AUTOMATIC OPERATION.
136 | Operation | MS15039/01E 2018-11
TIM-ID: 0000074303 - 001