151029 – FGT Fail High
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for operation.
u
Restart TecJet.
151030 – Delta P Fail High
Red alarm. Initiated by TecJet.
Cause
Corrective action
Excessive differential pressure
over TecJet detected.
1. Check gas pressure.
2. Check TecJet for dirt.
151031 – FGP Fail High
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for operation.
u
Restart TecJet.
151032 – Coil Current Fail High
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for operation.
u
Restart TecJet.
151035 – Position Fail High
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for operation.
u
Restart TecJet.
151036 – Elec Temp Fail Low
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for operation.
u
Restart TecJet.
151037 – FGT Fail Low
Red alarm. Initiated by TecJet.
Cause
Corrective action
Gas temperature before TecJet is
below the preset limit value.
u
Check TecJet and configuration.
MS150034/04E 2016-11
| Troubleshooting | 83
TIM-ID: 0000017543 - 001