151038 – Delta P Fail Low
Red alarm. Initiated by TecJet.
Cause
Corrective action
Differential pressure at TecJet is
below the preset limit value.
u
Check TecJet and configuration.
151039 – FGP Fail Low
Red alarm. Initiated by TecJet.
Cause
Corrective action
Gas pressure before TecJet is
below the preset limit value.
u
Check TecJet and configuration.
151040 – Coil Current Fail Low
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for operation.
u
Restart TecJet.
151043 – Position Fail Low
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for operation.
u
Restart TecJet.
151048 – Analog Input Low Error
Red alarm. Initiated by TecJet.
Cause
Corrective action
TecJet setting is not correct.
u
Check setting and switch over to PWM input. Check PWM signal.
151049 – Analog Input High Error
Red alarm. Initiated by TecJet.
Cause
Corrective action
TecJet setting is not correct.
u
Check setting and switch over to PWM input. Check PWM signal.
151050 – PWM Duty Cycle Low Error
Red alarm. Initiated by TecJet.
Cause
Corrective action
PWM signal is beyond the valid
range.
1. Check cabling.
2. Check frequency.
3. Check signal.
84 | Troubleshooting | MS150034/04E 2016-11