180 – AL CAN1 Node Lost
ZKP-Number:
Yellow alarm.
Associated parameter 2.0500.680
Cause
Corrective action
Bus node (SAM or EMU) lost on
CAN bus 1.
u
Check operation of nodes and cabling. Busses (CAN bus 1 and
CAN bus 2) are redundant.
181 – AL CAN2 Node Lost
ZKP-Number:
Yellow alarm.
Associated parameter 2.0500.681
Cause
Corrective action
Bus node (SAM or EMU) lost on
CAN bus 2.
u
Check operation of nodes and cabling. Busses (CAN bus 1 and
CAN bus 2) are redundant.
182 – AL CAN Wrong Parameters
ZKP-Number:
Red alarm.
Associated parameter 2.0500.682
Cause
Corrective action
Incorrect parameter values
entered in data record.
u
Contact Service (configuration fault).
183 – AL CAN No PU-Data
ZKP-Number:
Red alarm.
Associated parameter 2.0500.683
Cause
Corrective action
A CAN mode has been selected in
which communication with the PU
data module is initialized.
However, the required PU data
module is not available or not
valid.
u
Contact Service (configuration fault).
120 | Troubleshooting | MS150034/04E 2016-11