112703 – HIHI T-Exhaust A3 (abs)
Red alarm. Initiated by EMU.
Cause
Corrective action
Individual exhaust gas
temperature of this cylinder is
too high.
1. Check emission values.
2. Check ignition timing(→ Page 143).
3. Check valve drive (exhaust valves do not close).
112704 – HIHI T-Exhaust A4 (abs)
Red alarm. Initiated by EMU.
Cause
Corrective action
Individual exhaust gas
temperature of this cylinder is
too high.
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
112705 – HIHI T-Exhaust A5 (abs)
Red alarm. Initiated by EMU.
Cause
Corrective action
Individual exhaust gas
temperature of this cylinder is
too high.
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
112706 – HIHI T-Exhaust A6 (abs)
Red alarm. Initiated by EMU.
Cause
Corrective action
Individual exhaust gas
temperature of this cylinder is
too high.
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
112707 – HIHI T-Exhaust A7 (abs)
Red alarm. Initiated by EMU.
Cause
Corrective action
Individual exhaust gas
temperature of this cylinder is
too high.
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
112708 – HIHI T-Exhaust A8 (abs)
Red alarm. Initiated by EMU.
Cause
Corrective action
Individual exhaust gas
temperature of this cylinder is
too high.
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
MS150115/00E 2013-10
| Troubleshooting | 69
TIM-ID: 0000038611 - 002