112317 – HI T-Exhaust B7
Yellow alarm. Initiated by EMU.
Cause
Corrective action
The exhaust temperature of this
cylinder is too high as compared
with the average value.
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
112318 – HI T-Exhaust B8
Yellow alarm. Initiated by EMU.
Cause
Corrective action
The exhaust temperature of this
cylinder is too high as compared
with the average value.
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
112319 – HI T-Exhaust B9
Yellow alarm. Initiated by EMU.
Cause
Corrective action
The exhaust temperature of this
cylinder is too high as compared
with the average value.
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
112320 – HI T-Exhaust B10
Yellow alarm. Initiated by EMU.
Cause
Corrective action
The exhaust temperature of this
cylinder is too high as compared
with the average value.
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
112401 – LO T-Exhaust A1
Yellow alarm. Initiated by EMU.
Cause
Corrective action
The exhaust temperature of this
cylinder is too high as compared
with the average value.
1. Check spark plug.
2. Check emission values.
3. Check ignition timing (→ Page 143).
4. Check valve drive.
112402 – LO T-Exhaust A2
Yellow alarm. Initiated by EMU.
Cause
Corrective action
The exhaust temperature of this
cylinder is too high as compared
with the average value.
1. Check spark plug.
2. Check emission values.
3. Check ignition timing (→ Page 143).
4. Check valve drive.
MS150115/00E 2013-10
| Troubleshooting | 57
TIM-ID: 0000038611 - 002