1.4540.019 – Position Fail High
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart TecJet.
1.4540.020 – Elec Temp Fail Low
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart TecJet.
1.4540.021 – FGT Fail Low
Red alarm. Initiated by TecJet.
Cause
Corrective action
Gas temperature before TecJet
is below the preset limit value.
u
Check TecJet and configuration.
1.4540.022 – Delta P Fail Low
Red alarm. Initiated by TecJet.
Cause
Corrective action
Delta-p via TecJet below set limit
value.
u
Check TecJet and configuration.
1.4540.023 – FGP Fail Low
Red alarm. Initiated by TecJet.
Cause
Corrective action
Gas pressure before TecJet is
below the preset limit value.
u
Check TecJet and configuration.
1.4540.024 – Coil Current Fail Low
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart TecJet.
1.4540.025 – Position Fail Low
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart TecJet.
86 | Troubleshooting | MS150115/00E 2013-10
TIM-ID: 0000038611 - 002