Term
Unit
Value
Ambient temperature:
°C
-40 – +70 with circulating ambient air.
Storage temperature:
°C
-40 - +100
Relative humidity
%
5 – 97, no condensation.
Color:
Blue (RAL5015)
Material:
%
Polycarbonate, reinforced with 10 % fiberglass.
Dimensions:
mm
L x W x H (295 x 151 x 75)
Weight:
kg
Approx. 1.6
Note: Values stated above may be restricted when MCS 5 extension modules are used.
EMI/EMC – Electromagnetic interference (general)
The SAM has been tested according to the following standards and meets the relevant limit values:
Standard
Test
EN 55011
(Conducted emission) 10 kHz – 30 MHz, class A
EN 55011
(Radiated emission) 30 MHz – 1 GHz
IEC-60533:1999
(Conducted emission) 10 kHz – 30 MHz (type test)
EC-60533:1999
(Radiated emission) 150 kHz – 2 GHz (type test)
EN 61000-4-2
(ESD interference immunity) ±8 kV
EN 61000-4-3
(Radiated interference immunity) 80 MHz – 2 GHz
EN 61000-4-4
(Burst interference immunity) ±2 kV
EN 61000-4-5
(Surge interference immunity) ±1 kV/±2 kV
EN 50155
(Surge interference immunity) ±1.8 kV
EN 61000-4-17
(LF line-related interference) 0.03 – 10 kHz/3 Veff
EN 61000-4-29
(Line fluctuations/STANAG 1008)
IEC 60092-504
(Dielectric strength) 550 VAC/10 mA
EN 50155
(Isolation) 500 V/10 Mohm
Requirements for fulfillment of EMI/EMC limit values are as follows:
• If the housing is not grounded via the mounting plate, it must be connected to housing ground e.g. by
means of a cable with a minimum cross-section of 2.5 mm
2
. Cable length shall not exceed 10 cm.
• Only twisted-conductor cables may be used to connect sensors and actuators. The maximum length
of unshielded cables is 5 m, of shielded cables 50 m (provided wiring harness resistance allows for
this). Shielding shall be connected in the switchgear cabinet.