MSA AUER
MSA
Configuration
Control Unit Models 9010 LCD and 9020 LCD
19
GB
5.10 Jumpers predisposition
BASE BOARD - HARDWARE CONFIGURATIONS [normally performed in the factory]
The horn relay is normally unexcited with a normally open contact; if a normally closed contact is
desired, the track of CV 19, pos 2-3 needs to be cut and a drop of solder needs to be inserted in
pos.1-2.
Function
Component side /
solder side
NOTES
CV 13
A and B
pos. 1-2
RS485 redundant
Drop of solder
[component side]
CV 13
A and B
pos. 2-3
Drop of solder
[component side]
Configurations
reserved for MSA -
default: closed
CV 14
pos. 1-2
Configurations re-
served for MSA - de-
fault: open
Cv 15
pos. 1-2
Open - gen. purp. board
Closed - 4/20 mA board
Drop of solder
[component side]
Depending on the
board
CV 16
pos. 1-2
Open - 38400 baud
Closed - 9600 baud
Drop of solder
[component side]
Default: open -
[x RS485]
CV 17
pos. 1-2
Drop of solder
[component side]
Configurations
reserved for MSA -
default: open
CV 18
pos. 1-2
24 VDC power supply
generated within board
Jumper, component
side
e.g. for services
CV 18
pos 2-3
24 VDC power supply
from outside board
Jumper, component
side
e.g. for battery
backup
Default
CV 19
pos. 1-2
Horn contact n.c.
Drop of solder
[solder side]
Default: open
CV 19
pos. 2-3
Horn contact n.o.
Drop of solder
[solder side]
Default: closed
CV 20
pos. 1-2
Drop of solder
[component side]
Configurations
reserved for MSA -
default: open
CV 22
pos. 1-2
Opto-isolated caution
output
Drop of solder
[component side]
Needs an external
negative on
terminal 7
CV 22
pos. 2-3
Opto-isolated caution
output
Drop of solder
[component side]
The negative is
common to the de-
fault board
CV 23
pos. 1-2
Closed - ATEX version
Open - non-ATEX
version
Drop of solder
[component side]
Default: closed
CV 24
pos. 1-2
Closed - UC 9010
Open - UC 9020
Drop of solder
[component side]
CV 25
pos. 1-2
Watch-dog activation
Jumper, component
side
Default: closed
Summary of Contents for 9010 LCD
Page 1: ...Operating Manual CONTROL UNIT MODELS 9010 and 9020 LCD Order No 10093590 02 ...
Page 2: ...MSA AUER GmbH Thiemannstrasse 1 D 12059 Berlin Germany MSA AUER GmbH All rights reserved ...
Page 84: ...Control Unit Models 9010 LCD and 9020 LCD 84 Appendix MSA GB ...
Page 87: ......
Page 88: ......
Page 89: ......
Page 94: ......
Page 98: ......
Page 99: ......