5 Mounting
Maschinenfabrik Reinhausen GmbH 2015
103
4427410/00 EN
OILTAP® R
Moving on-load tap-changer to adjustment position
► Move on-load tap-changer to adjustment position.
Figure 118: Adjustment position
Removing on-load tap-changer head cover
WARNING
Danger of death or severe injury!
Danger of death or severe injury from explosive gases under the on-load
tap-changer head cover!
► Ensure that there are no naked flames, hot surfaces or sparks (for ex-
ample caused by static charging) in the immediate surroundings and
that none occur.
► De-energize all auxiliary circuits (for example tap-change supervisory
control, pressure relief device, pressure-operated relays) before remov-
ing the on-load tap-changer head cover.
► Do not operate any electric devices during the work (for example risk of
sparks caused by impact wrench).
► Only use conductive and grounded hoses, pipes and pump equipment
that are approved for flammable liquids.
NOTICE
Damage to the on-load tap-changer and transformer!
Small parts in the oil compartment may block the diverter switch insert,
thereby damaging the on-load tap-changer and transformer!
► Take care to avoid parts falling into the oil compartment.
► Check that you have the same number of small parts when disassem-
bling and reassembling.
5.3.8.2.1.1
5.3.8.2.1.2
Summary of Contents for OILTAP R