DCA220SSJU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (02/10/17) — PAGE 55
3Ø-480 VAC PARALLEL WIRING DIAGRAM
BLK (L1)
RED (L2)
BLUE (L3)
WHITE (NEU.)
GREEN (GND.)
GENERA
TOR #1
PARALLEL WIRING CONNECTIONS
VIA CAMLOKS DCA220SSJU4F
3-PHASE 480 VAC
MINIMUM CABLE SIZE IS 4/0.
NOTE:
1
2
1
ALL
FIVE CAMLOK P
AIRS
ARE
BONDED
.
2
PHASE A (U)
PHASE B (V)
PHASE C (W)
GENERA
TOR #2
LOAD
BLK (L1)
RED (L2)
BLUE (L3)
WHITE (NEU.)
GREEN (GND.)
3
POINT
OF CONNECTION/COMMON OUTPUT
BUS
POWER DISTRIBUTION P
ANEL.
3
SELECT
CORRECT
SIZE OF CABLES
TO HANDLE FULL
LOAD/AMPERAGE
(
528
AMPS @ 480 V
AC) OF GENERA
TOR.