DCA220SSJU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (02/10/17) — PAGE 41
GENERATOR SHUT-DOWN PROCEDURES
NORMAL SHUTDOWN PROCEDURE
To shutdown the generator, use the following procedure:
1. Place both the
MAIN, GFCI and LOAD circuit breakers
as shown in Figure 53 to the
OFF position.
Figure 53. Main, Aux. and GFCI
Circuit Breakers (OFF)
2. Let the engine cool by running it at low speed for 3-5
minutes with no load applied.
3. Place the
Auto Off/Reset Manual Switch (Figure 54)
in the
OFF/RESET position.
Figure 54.
Auto Off/Reset Manual
itch
(Off/Reset)
4. Verify that all status LEDs on the ECU control panel
are
OFF (not lit).
5. Remove all loads from the generator.
6. Inspect entire generator for any damage or loosening of
components that may have occurred during operation.
WARNING
NEVER stop the engine suddenly except in an
emergency.
AUTO
MANUAL
OFF/RESET
(CENTER)
EMERGENCY SHUTDOWN PROCEDURE
1. Place the
Auto Off/Reset Manual Switch (Figure 55)
in the
OFF/RESET position.
Figure 55.
Auto Off/Reset Manual
Sw
itch (OFF)
AUTO
MANUAL
OFF/RESET
(CENTER)