PAGE 56 — DCA220SSJU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (02/10/17)
3Ø-208 VAC PARALLEL WIRING DIAGRAM
BLK (L1)
BLUE (L3)
GENERA
TOR #1
PARALLEL WIRING CONNECTIONS
VIA CAMLOKS DCA220SSJU4F
3-PHASE 208 VAC
2
1
BLK (L1)
PHASE A (U)
PHASE B (V)
PHASE C (W)
GENERA
TOR #2
RED (L2)
WHITE (NEU.)
GREEN (GND.)
BLK (L1)
RED (L2)
BLUE (L3)
WHITE (NEU.)
GREEN (GND.)
3
MINIMUM CABLE SIZE IS 4/0.
NOTE:
1
ALL
FIVE CAMLOK P
AIRS
ARE
BONDED
.
2
POINT
OF CONNECTION/COMMON OUTPUT
BUS
POWER DISTRIBUTION P
ANEL.
3
LOAD
SELECT
CORRECT
SIZE OF CABLES
TO HANDLE FULL
LOAD/AMPERAGE (1200
AMPS @ 208 V
AC) OF GENERA
TOR.
MAIN CIRCUIT
BREAKER ON EACH UNIT
WILL
TRIP
A
T 600
AMPS
.
PHASE
A (U)
RED (L2)
PHASE B (V)
BLUE (L3)
PHASE C (W)
WHITE
(NEUTRAL)
GREEN (GND.)