PAGE 32 — DCA220SSJU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (02/10/17)
OUTPUT TERMINAL PANEL CONNECTIONS
UVWO TERMINAL OUTPUT VOLTAGES
Various output voltages can be obtained using the UVWO
output terminal lugs. The voltages at the terminals are
dependent on the placement of the jumpers plates (6) on
the
Voltage Change-Over Board and the adjustment of
the
Voltage Regulator Control Knob.
Remember the voltage change-over board determines the
range of the output voltage and can be configured in two
different positions that provide 6 different output voltages
at the UVWO output terminals. The generator is shipped
from the factory in the 240V configuration. The voltage
regulator (VR) allows the user to increase or decrease the
selected voltage.
3Ø-240V UVWO Terminal Output Voltages
1. Jumper the voltage change-over board for 240V
operation as shown in Figure 22
Figure 22. Voltage Change-Over Board
3Ø 240/139V Configuration
2. Connect the load wires to the UVWO terminals as
shown in Figure 23
Figure 23. UVWO Terminal Lugs
3Ø-240/1Ø-139 Connections
X
Y
Z
O
U
U
1
2
V
V
2
1
W
W
2
1
JUMPER
6 PLACES
1
2
3
4
5
6
O
U
V
W
BLACK
RED
BLUE
WHITE
GREEN
GROUND
CONNECTION
BE USED
AT ALL TIMES
MUST
THREE-PHASE
240 VAC (LOAD CONNECTIONS)
3. Turn the voltage regulator knob (Figure 24) clockwise
to increase voltage output, turn counterclockwise to
decrease voltage output. Use voltage regulator
adjustment knob whenever fine tuning of the output
voltage is required
Figure 24. Voltage Regulator Knob
1Ø-240V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered
for 240V operation as shown in Figure 22.
2. Connect the load wires to the UVWO terminals as
shown in Figure 25.
Figure 25. UVWO Terminal Lugs
1Ø-240V Connections
1Ø-120V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered
for 240V operation as shown in Figure 22.
2. Adjust voltage regulator knob (Figure 24) for an output
of 208V to obtain 120V at the UVWO terminals.
3. Connect the load wires to the UVWO terminals as
shown in Figure 26
Figure 26. UVWO Terminal Lugs 1Ø-120V
Connections
O
U
V
W
BLACK
RED
BLUE
WHITE
GREEN
GROUND
CONNECTION
BE USED
AT ALL TIMES
MUST
240V
240V
240V
SINGLE-PHASE
240 VAC (LOAD CONNECTIONS)
O
U
V
W
BLACK
RED
BLUE
WHITE
GREEN
GROUND
CONNECTION
BE USED
AT ALL TIMES
MUST
120V
120V
SINGLE-PHASE
120 VAC (LOAD CONNECTIONS)
120V