[37]
User Guidelines
– TCU-90L
12-06-2019
Vers. 003
16
Water quality
Depending on the unit to be cooled or heat-balanced, certain requirements have to be met by the cooling water regarding
its quality. In order to protect all parts of the unit against corrosion, Mouldpro recommends as a matter of principle to treat
the water with a suitable cleaning agent (anticorrosive as well as non-ferrous metal protector and hardness stabilizer). In
addition, depending on the materials installed, the temperatures and the type of process, the following water quality data
have to be met.
As a rule the following data apply:
HYDROLOGICAL DATA
MAX
UNIT
PH-value
7,5
– 8,5
-
Conductivity
< 150
mS/m
Total hardness
< 15
°dH
Carbonate hardness
< 4
°dH
Carbonate hardness in case of
stabilization of hardness
< 20
°dH
Chlorid Cl
<100
mg/l
Sulphate-So4
< 150
mg/l
Ammonium NH4
< 1
mg/l
Iron Fe
< 0,2
mg/l
Manganese
< 0,1
mg/l
free from solids
Furthermore the following applies:
Systems with stainless steel
Systems with aluminium
PH-value
min. 7,0
max. 8,0
Temperatures below 5°C
o
When employing chillers at temperatures below + 5°C, an anti-freeze medium with corrosion inhibitor
must be added.
Temperatures over 120°C
o
At water temperatures over 120°C glycol may not be used.
If the recommended water qualities are not met, the components of the unit will be damaged due to corrosion. Mouldpro
will not accept any liability for any such damages
Chlorid Cl
Temp. < 50 °C
max. 100
mg/l
Chlorid Cl
Temp. 50 up to 90 °C
max. 50
mg/l
Chlorid Cl
Temp. > 90 °C
max. 30
mg/l
Summary of Contents for TCU-90L
Page 10: ... 10 User Guidelines TCU 90L 12 06 2019 Vers 003 3 2 Rear view ...
Page 38: ... 38 User Guidelines TCU 90L 12 06 2019 Vers 003 17 Electrical diagram ...
Page 39: ... 39 User Guidelines TCU 90L 12 06 2019 Vers 003 18 Water Circuit Diagram ...
Page 40: ... 40 User Guidelines TCU 90L 12 06 2019 Vers 003 19 Control Circuit diagram ...
Page 41: ... 41 User Guidelines TCU 90L 12 06 2019 Vers 003 20 Components and spare part list ...
Page 42: ... 42 User Guidelines TCU 90L 12 06 2019 Vers 003 ...