IX34208a_e.doc / Aug-09
Page 36 / 40
7.2. Technical Specifications
Supply voltage DC
: 24 V (17 – 30 V)
Consumption (without sensor)
: 17 V: 190 mA, 24 V: 150 mA, 30 V: 120 mA
Aux. output for encoder
: 24 VDC, +/- 15%, 120 mA (with AC and DC supply)
Control Inputs
: 3 (PNP/NPN/Namur), A / B = unused, C = Reset
Input currents
: 5.1 mA / 24 V (Ri = 4,7 kOhm)
Input level HTL
: Low: 0 ... 2 V, High: 9 ... 35 V
SSI input frequency range
: 100 Hz – 1 MHz
Min. pulse duration for Reset
: 5 msec
Serial interface
: RS 232 or RS 485 (switch selectable)
600 ... 38400 bauds
Ambient temperature
: Operation: 0° - 45°C ( 32 – 113°F)
Storage: -25° - +70°C (-13 – 158°F)
Housing
: Norly UL94 – V-0
Display
: 6 decades, LED, high- efficiency orange, 15 mm (0.59’’)
Protection class
: Front IP65, Rear IP20
Terminal cross section
: Signals max. 1.5 mm², AC power max. 2.5 mm²
Output Relays
: 2 relays with dry changeover contacts
250 VAC / 1 A / 250 VA or 100 VDC / 1 A / 100 W
Conformity and Standards
: EMC 2004/108/EC:
EN 61000-6-2
EN
61000-6-3
LV 2006/95/EC:
EN 61010-1