Switching -Menu
(Switching characteristics of the relays/outputs)
Code
Setting Range
Default
Lock Relay /Switching Output
Assignment of a catch function to the relays *)
„H0“
0..15
0
0
No catch function for any of the relays
1
Relay 1/output 1 with catch (release by key/control input)
2
Relay 2/output 2 with catch (release by key/ control input)
3
Relays 1&2/output 1&2 with catch (release by key/control input)
4
Relay 3/output 3 with catch (release by key/control input)
5
Relays 1&3/output 1&3 with catch (release by key/control input)
6
Relays 2&3/output 2&3 with catch (release by key/control input)
7
all Relays/outputs with catch (release by key/control input)
8-
15
similar to 0 - 7, but catch to release by key/by control input and
automatically upon standstill
Standstill Time
Time setting for standstill definition
A time of xx.xx seconds after detection "zero input frequency" the unit
signals "standstill" and re-activates the start-up-delays
„H1“
0..99.99
0
Relay / Switching Output Action
(for more details see section
9.3
)
Selection of the relays/transistor outputs of which the switching state
should be overridden by key command or remote command (non-
selected relays will continue normally)
„K8“
0…8
0
0 No relay/transistor output selected
1 Relay 1/transistor output 1
2 Relay 2/transistor output 2
3 Relays 1 & 2/transistor output 1&2
4 Relay 3/transistor output 3
5 Relays 1 & 3 /transistor output 1&3
6 Relays 2 & 3/transistor output 2&3
7 All relays/transistor outputs selected
8 Freeze actual switching state of all relays/transistor outputs
*) According to parameter settings, the catch situation can be released by either pressing one of the front
keys or by a remote control signal or automatically upon detection of standstill (see "Command menu").