Dz260_05a_oi_e.doc / Dez-16
Page 21 / 40
Encoder-Menu
Code
Setting Range
Default
Sampling Time
Internal time base for sampling of the input frequency (sec.)
„A2“
0.001..9.999
0.001
Wait Time
Time to wait before unit detects zero speed (sec.)
Impulse distances greater than this time will be takes as zero
„A3“
0.01..9.99
1.00
Filter
Digital filter for smoothing of unstable frequencies
„A4“
0..7
0
0
Filter off
(very fast response to frequency changes)
1
Τ
(63%) = 1,9 msec. with Sampling Time = 1msec.
2
Τ
(63%) = 3,8 msec. with Sampling Time = 1msec.
etc.
7
Τ
(63%) = 122 msec. with Sampling Time = 1msec.
(very slow response to frequency changes)
Set Value
Fixed frequency set value for encoder simulation (Hz)
(see also "Command"-Menu)
„A5“
-1 000 000.0 ...
+1 000 000.0
0
7.2.3.
Serial Readout Menu
An actual value proportional to the input frequency can be read out via serial link, accessing the
serial readout register (code :8 ). As a Basic Value this register uses the scaling set for the analog
output, i.e. a range from 0 to 10 000 units corresponding to 0 - 100,00 % of the full scale output
(see section
7.2.7
"Analog Menu"). This readout can still be rescaled to user-friendly engineering
units, using the following parameters:
Serial Readout Menu
Code
Setting Range
Default
Multiplier
„A8“
-9.9999 … +9.9999
+1.0000
Divider
„A9“
0.0000 … 9.9999
0.0000
Offset
(absolute term)
„B0“
-99999999 … +99999999
0
Readout (:8) = Basic Value x
Multiplier
Divider
+ Offset
The definition of the "Basic Value" occurs in the "Analog Menu" and is also available
for the DZ267 units without analog output
the ratio Multiplier / Divider must never be greater than 15 000
Setting "Divider" to zero will skip the rescaling procedure, resulting in a shorter
response time with all functions of the unit
More details about serial communication can be found in the appendix.