Serial -Menu
(Configuration of the serial link)
Code
Setting Range
Default
Serial Protocol
Determines the sequence of characters sent, when you use the serial
output for cyclic data transmission under timer control
(xxxxxxx is the measuring value transmitted).
„F3“
0 ... 1
0
0=
Transmission = Unit Nr. – Data, LF, CR
1=
Transmission = Data, LF, CR
Setting "1" removes the unit address from the string which allows a
slightly faster transmission cycle.
Unit No.
0: 1 1 +/- X X X X X X LF CR
1:
+/- X X X X X X LF CR
Serial Timer
T
his register determines the cycle time in seconds for cyclic
transmission when the Printer Mode is switched on.
With setting “0” all cyclic transmission is switched off and the unit will
only send data upon request (PC mode).
„F4“
0 ... 9.99
0
Register Code
Serial access code of the register which, in Printer Mode, should be
transmitted with every cycle. The most important registers are shown
below.
Setting
Code Register contents
7
:7
Actual analog output value
10000 = 10 V = 20 mA
8
:8
User-defined readout value
(see
7.2.3
)
9
:9
Frequency detected on the input
(Scaling is 0.1 Hz)
11
;1
Actual LCD display value
„F5“
0 ... 19
(:0) … (;9)
8